Inspection
Inspection Details
Equipment ID
14318
14318
Inspection Date
8/13/2024
8/13/2024
Inspection Type
Reinspection
Reinspection
Inspector Name
Kevin Hecht
Kevin Hecht
Mechanic Name
Tom Worsham
Tom Worsham
Relief Valve Pressure
NA
NA
Slide
C: 12"; CW: 13"
C: 12"; CW: 13"
Governor Rope Pull
C: 75/450; CW:88/510
C: 75/450; CW:88/510
Door Closing Force
22
22
External ID
92a70b4f-7028-4787-ae95-2139c8d74c89
92a70b4f-7028-4787-ae95-2139c8d74c89
Location
St. Louis Hills Assisted Living & Memory Care
6543 Chippewa St, St. Louis, MO
Phone: (314) 647-6600
6543 Chippewa St, St. Louis, MO
Phone: (314) 647-6600
Owner
Attn: Tyler Moss
St. Louis Hills Assisted Living & Memory Care
6543 Chippewa St, St. Louis, MO 63109
Phone: (314) 647-6600
Email: tyler@stlhillsliving.com
St. Louis Hills Assisted Living & Memory Care
6543 Chippewa St, St. Louis, MO 63109
Phone: (314) 647-6600
Email: tyler@stlhillsliving.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 4.5 - Access to Hoistway | 8.11.2.1.4(e) | Yes | No | Make top floor access switch operational. | 11/26/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.16 - Traveling cables and junction boxes | 8.11.2.1.3(v) | Yes | No | Secure all hoistway junction box covers. | 11/26/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.5 - Housekeeping | 8.11.2.1.2(e) (Re-Inspection) | Yes | No | Remove all unused and old equipment from the machine room. | 11/26/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.11.2.1.4(l) | Yes | Yes | Make flashing fire hat operational. | 11/26/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.11 - Disconnecting Means and Control | 2.26.4 | Yes | No | Provide permanent wiring for 110v source to controller. | 11/26/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.8 - Pipes, wiring, and ducts | 8.11.2.1.2(h) | Yes | No | Secure all duct and junction box covers and secure all conduit runs. | 11/26/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Display a copy of the current state operating certificate. | 3/18/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO state operating certificate shall be posted in the elevator machine room. | 12/15/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The in car emergency telephone shall be operational. | 1/11/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. Evacuation procedures are missing. (This item is for notification purposes for future violation in 2022) | 11/16/2021 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Inspection incomplete due to counterweight safeties not releasing. Only able to run the hoistway. All other items of the annual inspection and category 5 test need to be completed. | 7/8/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.17 - Drive machine brake | 8.6.4.19.11 A17.1 2016 Ascending Overspeed Protection, Unintended Movement Devices, and Emg Brake | Yes | Yes | Rope gripper is not working. Elevator Red Tagged. | 8/13/2024 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Safety slide measurement of car and counterweight shall be obtained. | 8/13/2024 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO state operating certificate shall be displayed in the elevator machine room. | 5/26/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) | No | No | A current MCP is required in the machine room for each unit including maintenance, repair, and fire service testing logs. | 5/26/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | A current ABC rated fire extinguisher shall be provided in the machine room. | 5/26/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Audible signal and emergency car illumination not working properly when 110v power is disconnected. | 2/10/2026 |