Inspection
Inspection Details
Equipment ID
2163
2163
Inspection Date
8/23/2024
8/23/2024
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Ronald Edwards
Ronald Edwards
Mechanic Name
Anthony Henthorne
Anthony Henthorne
Relief Valve Pressure
440
440
Slide
n/a
n/a
Governor Rope Pull
n/a
n/a
Door Closing Force
25
25
External ID
46ab1652-fe8f-47b6-a56f-0abe559a0b36
46ab1652-fe8f-47b6-a56f-0abe559a0b36
Location
Welcome Inn
3300 NW Jefferson St, Blue Springs, MO
Phone: (816) 622-8171
3300 NW Jefferson St, Blue Springs, MO
Phone: (816) 622-8171
Owner
Attn: Elaina
3300 NW Jefferson, LLC
3700 Monterry Dr, Ste A, Columbia, MO 65203
Phone: (816) 200-6585
Email: elaina@goldengroverei.com
3300 NW Jefferson, LLC
3700 Monterry Dr, Ste A, Columbia, MO 65203
Phone: (816) 200-6585
Email: elaina@goldengroverei.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | conversion - reinspect | Yes | No | Car top needs to be cleaned has excess Rubbish on top | 9/7/2017 |
| conversion | conversion | conversion - reinspect | Yes | No | pit needs to be cleaned | 9/7/2017 |
| conversion | conversion | conversion - reinspect | Yes | No | Emg. Lt. ,Bell an Phone not working | 9/7/2017 |
| conversion | conversion | conversion - reinspect | Yes | No | Broken car top lt. socket | 9/7/2017 |
| conversion | conversion | conversion - reinspect | Yes | No | Car top lt fixture Broken | 8/24/2018 |
| conversion | conversion | conversion - reinspect | Yes | No | Clean Pit | 8/24/2018 |
| conversion | conversion | conversion - reinspect | Yes | No | Car top needs cleaned | 8/24/2018 |
| MO Minimum : Elevators | (G)2-Alterations | 8.7.2.14.2 Car Enclosure | Yes | No | emg lt not working | 9/1/2020 |
| MO Minimum : Elevators | (S) - Fire Service | (S)1 | Yes | Yes | no fire serv signage phase one | 9/1/2020 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | pit has paper an other debris needs cleaning | 11/4/2020 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)5 (Machine Room Lighting) | No | No | Mach room lt bulb needs repaired or replaced inadaquit lighting | 11/4/2020 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)8 Car Lighting | No | No | car lights not working | 11/4/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | need proper MCP | 11/4/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | no phone no emg lt no bell working. unit has no phone | 9/4/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | phone anemg. lt. not working | 9/21/2020 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)5 (Machine Room Lighting) | No | No | Mach room lts not working properly | 11/4/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | Car top lt .fixture broken | 11/4/2020 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)8 Car Lighting | No | No | car lts not working | 8/3/2022 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | mach.room door lock is defeatable | 9/21/2023 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | no current cirt posted | 9/21/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | no phone but emg lt. an bell not working . | 9/21/2023 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | pit needs cleaned | 12/5/2024 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | machroom door not self closing | 2/5/2025 |