Inspection
Inspection Details
Equipment ID
2047
2047
Inspection Date
8/27/2024
8/27/2024
Inspection Type
Reinspection
Reinspection
Inspector Name
Michael Elder
Michael Elder
Mechanic Name
Jasen Kennedy
Jasen Kennedy
Relief Valve Pressure
NA
NA
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
NA
NA
External ID
db1af7f1-e9c3-4ad4-88ff-e788d491ebdc
db1af7f1-e9c3-4ad4-88ff-e788d491ebdc
Location
Lee's Summit High School
400 SE Blue Pkwy, Lee's Summit, MO
Phone: (816) 986-2000
Email: matthew.tillman@lsr7.net
400 SE Blue Pkwy, Lee's Summit, MO
Phone: (816) 986-2000
Email: matthew.tillman@lsr7.net
Owner
Attn: Nick Mathews
Lee's Summit R-7 School District
502 Transport Dr, Lee's Summit, MO 64081
Phone: (816) 986-2173
Email: nick.mathews@lsr7.net
Lee's Summit R-7 School District
502 Transport Dr, Lee's Summit, MO 64081
Phone: (816) 986-2173
Email: nick.mathews@lsr7.net
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)8 Car Lighting | No | No | Overhead lighting in car inadequate, and unguarded. | 3/26/2026 |
| MO Minimum : Elevators | (G)2-Alterations | 8.7.2.14.2 Car Enclosure | Yes | No | Emergency phone not identifying location of call. | 1/19/2021 |
| MO Minimum : Elevators | (G)2-Alterations | 8.7.2.14.2 Car Enclosure | Yes | No | Emergency lights not working. | 1/19/2021 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | No | No | Emergency phone not identifying the location. | 1/19/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone not working, alarm bell ok. | 1/19/2023 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current operating certificate in machine room. | 3/26/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.1.6.3 Controllers ,Wiring and Wiring Diagrams | No | No | Connection loose on controller starter box din rail. | 3/26/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.11.1 Firefighters' Emergency Operation & Documentation | No | No | Fire service testing log not up to date. | 3/26/2026 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)8 | No | No | Provide covers for FFS modules in machine room. | 3/26/2026 |
| A17.1-2016 : Elevators | 2.1 - Access to machine space | 2.7.3.4 | No | No | Machine room door must be self-closing | 3/26/2026 |
| A17.1-2016 : Elevators | 1.6 - Car emergency signal | 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone not being answered | 4/1/2024 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | Yes | No | Shunt trip not overriding battery lowering. Need relay added | 4/1/2024 |
| A17.1-2016 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.6.4.19.6 | Yes | No | Top hoistway smoke sensor recalls elevator to wrong floor. Need relay added | 4/1/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone not working, alarm bell ok. | 3/26/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone not working, alarm bell ok. |