Inspection
Inspection Details
Equipment ID
12261
12261
Inspection Date
8/23/2024
8/23/2024
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Sean Carmody
Sean Carmody
Mechanic Name
Jeffrey Miller
Jeffrey Miller
Relief Valve Pressure
480
480
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
18
18
External ID
3d1ea762-f663-4bb0-aafa-224093ccdcc2
3d1ea762-f663-4bb0-aafa-224093ccdcc2
Location
Life Care Center
3520 Chouteau Ave, St. Louis, MO
Phone: (314) 771-7667
3520 Chouteau Ave, St. Louis, MO
Phone: (314) 771-7667
Owner
Attn: Life Care Center
Life Care Center
3520 Chouteau Ave, St. Louis, MO 63103
Phone: (000) 000-0000
Email: Melissa_schuettler@lcca.com
Life Care Center
3520 Chouteau Ave, St. Louis, MO 63103
Phone: (000) 000-0000
Email: Melissa_schuettler@lcca.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | Provide onsite maintenance documents. | 3/25/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) | 3/25/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing | No | No | The presence of an overspeed valve has been confirmed, along with an installation date of 2018. The overspeed valve shall be scheduled for a category 5 test on or before the next annual inspection. | 9/15/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 3.26.10 (Auxiliary Power)(Re-Inspection) | Yes | No | Battery lowering shall work. UPS is missing. Take corrective action as needed. | 7/12/2024 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | Two-way communication device shall work. It is currently giving a busy/off signal. | 7/12/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13 - Door systems | No | No | Replace missing up-thrust roller bearings on hoistway doors. | 7/18/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) | No | No | MCP, including PM records and monthly fire service test log, not being properly documented. | 7/18/2024 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | The pit shall be kept clean. | 9/26/2025 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Battery Lowering shall work. | |
| MO Minimum : Elevators | (S) - Fire Service | 8.6.11.1 Monthly Test and Log | No | No | MCP - Fire Service must be tested and properly documented monthly on Log Sheet | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | Replace damaged upthrust roller bearing, 1st floor. |