Inspection
Inspection Details
Equipment ID
22315
22315
Inspection Date
10/30/2018
10/30/2018
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Edward Balsat
Edward Balsat
Mechanic Name
Phillip Moise, Jr.
Phillip Moise, Jr.
Relief Valve Pressure
420
420
Slide
Governor Rope Pull
Door Closing Force
22
22
External ID
f4ad8370-7f6e-4d4b-9d29-d86e037493fb
f4ad8370-7f6e-4d4b-9d29-d86e037493fb
Location
Godwall
600 NW PLAZA DR, SAINT ANN, MO
600 NW PLAZA DR, SAINT ANN, MO
Owner
Godwall LLC
600 NW PLAZA DR, SAINT ANN, MO 63074-2204
600 NW PLAZA DR, SAINT ANN, MO 63074-2204
Billing
Attn: Godwall LLC
600 NW PLAZA DR, SAINT ANN, MO 63074-2204
600 NW PLAZA DR, SAINT ANN, MO 63074-2204
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.1 - Access to machine space | 2.7.3.4 | No | No | The machine room door is damaged and will not lock. The door shall be repaired or replaced and shall be self-locking. | 4/27/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.7 - Fire Extinguisher | 8.6.1.6.5 | No | No | A current fire extinguisher shall be installed in the machine room. | 4/27/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. Evacuation procedures are missing. (This item is for notification purposes for future violation in 2022) | 11/23/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.37 - Pressure Switch | 3.26.8 Pressure Switch | Yes | No | The low pressure switch shall be operational. When cylinders are installed with top of the cylinder above the top of the storage tank , a pressure switch shall be provided in the line between the cylinder and the valve, which shall be activated by the loss of positive pressure at the top of the cylinder. | 12/7/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 3.26.10 (Auxiliary Power)(Re-Inspection) | Yes | No | The auxiliary power lowering operation shall be tested. | 12/11/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.5.5.2 Oil Leakage Collection | No | No | A written record shall be kept of the quantity of hydraulic fluid added to the system and emptied from leakage collection containers and pans, shall not exceed 5 gal before removal, shall be covered, and shall not be permitted to overflow. Note: Per the State of Missouri: "The use of oil recovery systems to return the hydraulic fluid back into the main reservoir by automatic means or by gravity feed prevents proper monitoring of the gland packing and seals, and machine rooms can not be used as containment areas." | 12/5/2023 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | This annual test needs to be performed in its entirety. The only item that was tested was the relief valve. During this test, a significant leak developed in the muffler, which prevented any other required items from being tested. The relief test needs to be performed again because the leak could have affected the pressure reading. | 11/19/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.3.2 | No | No | Buckets shall be added in pit to measure oil. | 12/30/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.11.2.2.6 Fire Fighters Operation (Re-Inspection) | Yes | No | Phase II fire service shall work. | 12/30/2025 |