Inspection
Inspection Details
Equipment ID
16833
16833
Inspection Date
9/5/2024
9/5/2024
Inspection Type
Alteration
Alteration
Inspector Name
Michial Linenfelser
Michial Linenfelser
Mechanic Name
Jeff Setchfield
Jeff Setchfield
Relief Valve Pressure
Na
Na
Slide
Na
Na
Governor Rope Pull
Na
Na
Door Closing Force
Na
Na
External ID
133b719d-4957-4f00-8c47-c03b4cdb77b8
133b719d-4957-4f00-8c47-c03b4cdb77b8
Location
Cardinal Glennon Childrens Hospital
1465 S Grand Blvd, St. Louis, MO
Phone: (314) 268-2771
Alt Phone: (314) 591-1407
Fax: (314) 577-5314
Email: fred.carr1@ssmhealth.com
1465 S Grand Blvd, St. Louis, MO
Phone: (314) 268-2771
Alt Phone: (314) 591-1407
Fax: (314) 577-5314
Email: fred.carr1@ssmhealth.com
Owner
Attn: Madison Himelright
SSM Health- ESEP Department
1015 Corporate Square, Ste 160, St. Louis, MO 63132
Phone: (314) 577-5307
Email: madison.himelright@ssmhealth.com
SSM Health- ESEP Department
1015 Corporate Square, Ste 160, St. Louis, MO 63132
Phone: (314) 577-5307
Email: madison.himelright@ssmhealth.com
Billing
Attn: Fred Carr
SSM-Cardinal Glennon Childrens Hospital
1465 S Grand Blvd, St. Louis, MO 63104
Phone: (314) 268-2771
Alt Phone: (314) 591-1407
Fax: (314) 577-5314
Email: fred.carr1@ssmhealth.com
SSM-Cardinal Glennon Childrens Hospital
1465 S Grand Blvd, St. Louis, MO 63104
Phone: (314) 268-2771
Alt Phone: (314) 591-1407
Fax: (314) 577-5314
Email: fred.carr1@ssmhealth.com
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | The car top inspection station does not operate as designed and would not operate properly. The device shall be repaired or replaced to operate as designed. | 9/3/2019 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)3 | No | No | The top emergency exit has been impeded by electrical conduit added to the car for security cameras and cannot be opened. Remove conduit to allow escape hatch to be opened for maintenance and emergency personnel. | 10/20/2020 |
| A17.1-2016 : Elevators | 3.28 - Counterweight and counterweight buffer | 8.11.2.1.3(m) | No | No | There is a top guide roller on the counterweight that has deteriorated and shall be replaced. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13 - Door systems | No | No | A number of floors were missing the fire retaining tabs on the hoistway doors, install fire retaining tabs as required. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13 - Door systems | No | No | A number of floors were missing the fire retaining tabs on the hoistway doors, install fire retaining tabs as required. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) | No | No | There shall be maintenance records kept in the elevator machine room accessible to the inspector depicting dates and descriptions of maintenance tasks performed, callbacks, examinations, tests, adjustments, replacements and wiring diagrams. This shall be in accordance to the requirements in the Maintenance Control Program. Electronic means has NOT been approved by the State of Missouri. | |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | The testing has not been completed on the elevator at this time. The weight test shall be performed, safeties set, fireman’s service, emergency power, and car buffer compressed before the inspection is completed. | 7/9/2025 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Full load test was never completed last year. Perform the following tests to complete full load test: test drive machine brake with 125% of rated load, car safeties at rated speed with rated load, car buffer test at rated speed with rated load, counterweight buffer test at rated speed, need to test elevator for operation on emergency power, test phase I & II fire service. Re-inspection required | 7/28/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.2.1 Repair Parts | No | No | Elevator machine room air conditioner does not work. Repair to keep equipment in correct operating temperature | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Elevator cab phone does not work on battery back-up, need to replace phone battery. Re-inspection required | 7/28/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - Door Systems 8.6.4.13 (Re-Inspection) | Yes | No | A number of floors were missing the fire retaining tabs on the hoistway doors, install fire retaining tabs as required. | 7/28/2025 |
| A17.1-2016 : Elevators | 2.17 - Drive machine brake | 8.6.4.20.10 | Yes | Yes | Elevator traction machine failed to safely lower and hold 125% of the rated load due to brake failure, Elevator red-tagged and removed from service, Need to repair brake system. Re-inspection required before use. | 9/5/2025 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Need to test elevator for operation on emergency power and test phase I & II fire service. Re-inspection required | 9/5/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | No | No | A number of floors were missing the fire retaining tabs on the hoistway doors. Need to install tabs | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Elevator cab phone does not work on battery back-up, need to replace phone battery. Re-inspection required | 9/5/2025 |
| A17.1-2016 : Elevators | 2.17 - Drive machine brake | 8.6.4.20.10 | Yes | Yes | Re-inspection to perform 125% brake test. Elevator failed to safely lower and hold 125% of rated load, Elevator mechanic tried to make necessary repairs, but the elevator stopped running due to mechanical failure. Elevator remains Red-tagged. Re-inspection required | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13 - Door systems | No | No | A number of floors were missing the fire retaining tabs on the hoistway doors, install fire retaining tabs as required. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Elevator cab phone does not work on battery back-up, need to replace phone battery. Re-inspection required | |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Need to test elevator for operation on emergency power and test phase I & II fire service. Re-inspection required |