Inspection
Inspection Details
Equipment ID
5519
5519
Inspection Date
9/10/2024
9/10/2024
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
James VanZant
James VanZant
Mechanic Name
Shaun Deckard
Shaun Deckard
Relief Valve Pressure
350
350
Slide
Governor Rope Pull
Door Closing Force
15
15
External ID
162abbb9-faf5-472a-abef-2192d2128dcc
162abbb9-faf5-472a-abef-2192d2128dcc
Location
Murphy Manor
128 WALL ST, JOPLIN, MO
Phone: (417) 624-4514
128 WALL ST, JOPLIN, MO
Phone: (417) 624-4514
Owner
Attn: Matt Moran
Joplin Housing Authority
1834 W 24th St, Joplin, MO 64804
Phone: (000) 000-0000
Email: mmoran@joplinpha.org
Joplin Housing Authority
1834 W 24th St, Joplin, MO 64804
Phone: (000) 000-0000
Email: mmoran@joplinpha.org
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)12 (Door open zones) | Yes | No | 1.18 door restrictor needs repaired | 10/9/2018 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection) | Yes | No | 8.6.4.13.1(l) door restrictor needs repaired | 10/7/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.3.2.1 Phase 1 Emergency Recall OperationBy Fire Alarm initiating Devices | Yes | Yes | temporary under construction | 10/20/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.18 - Restricted opening of car or hoistway doors | 2.12.5 Restricted Opening of Hoistway or Car Doors (Re-Inspection) | Yes | No | Car Door restrictor shall work. (less than 4" opening) (REINSPECTION WITHIN 30 DAYS) | 2/26/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.18 - Restricted opening of car or hoistway doors | 2.12.5 Restricted Opening of Hoistway or Car Doors (Re-Inspection) | Yes | No | Car Door restrictor shall work. (less than 4" opening) (REINSPECTION WITHIN 30 DAYS) | 2/26/2021 |
| A17.1-2016 : Elevators | 1.6 - Car emergency signal | 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Alarm and light shall work with power loss. | 10/22/2021 |
| A17.1-2016 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.8 Switch Keys | No | No | Hall phase 1 switch shall be FEOK1 and Bezel shall be “reset,off,on” | 10/22/2021 |
| A17.1-2016 : Elevators | 1.6 - Car emergency signal | 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Alarm and light shall work with power loss. | 10/22/2021 |
| A17.1-2016 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.8 Switch Keys | No | No | Hall phase 1 switch shall be FEOK1 and Bezel shall be “reset,off,on” | 10/22/2021 |
| A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.2.1(a) | No | No | Compliant/Required Documentation & MCP shall be kept in equipment room(neat/organized) including Wiring Diagrams, Oil log &Fire service log, recorded monthly | 9/15/2022 |