Inspection
Inspection Details
Equipment ID
16973
16973
Inspection Date
9/11/2024
9/11/2024
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Mitchell McNeely
Mitchell McNeely
Mechanic Name
Richard King
Richard King
Relief Valve Pressure
450
450
Slide
Governor Rope Pull
Door Closing Force
22
22
External ID
e2879fc4-460f-4fe7-9484-bf00a3244164
e2879fc4-460f-4fe7-9484-bf00a3244164
Location
Missouri Botanical Garden- The Bertha Pfavtch Annex Bldg.
2236 Tower Grove Ave, St. Louis, MO
Phone: (314) 577-0844
Email: jackie.maciekowicz@mobot.org
2236 Tower Grove Ave, St. Louis, MO
Phone: (314) 577-0844
Email: jackie.maciekowicz@mobot.org
Owner
Attn: Missouri Botanical Garden
Missouri Botanical Garden
4344 Shaw Blvd, St. Louis, MO 63110
Phone: (314) 577-5130
Email: gsinvoices@mobot.org
Missouri Botanical Garden
4344 Shaw Blvd, St. Louis, MO 63110
Phone: (314) 577-5130
Email: gsinvoices@mobot.org
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-1996 : Elevators | 1.5 - Car lighting and receptacles | 204.7a (3)(a) Standby Illumination in the car. (Re-Inspection) | Yes | No | The emergency light fixture inside the elevator is not operational and shall be repaired. This is a reoccurring deficiency that may indicate that the charging system for the emergency battery is not operating as designed. | 2/7/2020 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | This is a reoccurring deficiency that may indicate that the charging system for the emergency battery is not operating as designed. | 2/7/2020 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The elevator ADA telephone inside the elevator is not giving the address. Check and repair the programming of this phone for proper operation and passenger safety. | 2/7/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6 General Maintenance Methods | No | No | The battery back–up lowering device was tested and did not operate as designed, the elevator failed to return to a lower floor and open its doors. Repair the device to operate as it is designed. | 1/7/2021 |
| A17.1-2016 : Elevators | 5.15 - Overspeed Valve | 8.6.5.16.5 | No | No | This elevator has an overspeed valve device installed that is not sealed and is now required to have a 5 year full load test performed. This requirement is due to the State of Missouri adopting the A17.1 2016 version of the elevator safety code. Reinspection is required. | 11/1/2021 |
| A17.1-1996 : Elevators | 1.5 - Car lighting and receptacles | 204.7 | No | No | The cab ceiling is of the open egg-crate type, which does not provide protection from the light bulbs should they shatter. The lights shall be guarded by plastic sleeve or some other means to properly protect passengers. | 2/15/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6 General Maintenance Methods | No | No | The battery back–up lowering device was tested and did not operate as designed, the elevator failed to return to a lower floor and open its doors. Repair the device to operate as it is designed. | 2/15/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone in car did not work, appeared to have no live phone line, needs repaired. Re-inspection required | 4/2/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6 General Maintenance Methods | Yes | No | The emergency battery lowering device does not appear to work as designed, needs repaired. Re-inspection required | 4/2/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone in car did not work, appeared to have no live phone line, needs repaired. Re-inspection required | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6 General Maintenance Methods | Yes | No | The emergency battery lowering device does not appear to work as designed, needs repaired. Re-inspection required |