Inspection
Inspection Details
Equipment ID
5820
5820
Inspection Date
11/14/2018
11/14/2018
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Daniel Letcher
Daniel Letcher
Mechanic Name
Timothy Robinson
Timothy Robinson
Relief Valve Pressure
400
400
Slide
Governor Rope Pull
Door Closing Force
10
10
External ID
4fd3bc3c-3f0e-46c7-940c-6b9770b6d98d
4fd3bc3c-3f0e-46c7-940c-6b9770b6d98d
Location
Sycamore Hills Elementary
15208 E 39TH ST S, INDEPENDENCE, MO
15208 E 39TH ST S, INDEPENDENCE, MO
Owner
Attn: Independence School District
Independence School District
201 N FOREST AVE, INDEPENDENCE, MO 64050
Phone: (000) 000-0000
Independence School District
201 N FOREST AVE, INDEPENDENCE, MO 64050
Phone: (000) 000-0000
Billing
Attn: Independence School District
Independence School District
201 N FOREST AVE, INDEPENDENCE, MO 64050
Phone: (000) 000-0000
Email: Geri_frink@isdschools.org
Independence School District
201 N FOREST AVE, INDEPENDENCE, MO 64050
Phone: (000) 000-0000
Email: Geri_frink@isdschools.org
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (S) - Fire Service | (S)1 | Yes | No | provide key onsite for the fire service keyswitch, could not test fire service | 3/28/2019 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | maintain dry pit, at the time of the inspection there was standing water in the pit | 2/11/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | No | No | replace the emergency light battery, it is dead | 3/28/2019 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | Repair the top of car inspection station, it would not run in the down direction | 2/11/2020 |
| MO Minimum : Elevators | (S) - Fire Service | (S)1 | Yes | No | repair fire service phase 1 keyswitch, it did not recall the elevator | 8/6/2019 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | replace emergency light battery, it is dead | 2/11/2020 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | the pit shall be kept dry. | 11/3/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | The Maintenance Control Program (MCP) On-Site documents are not in the machine room. | 1/3/2022 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | standing water in the pit, maintain a dry pit | 1/3/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | cortop work light bulb is missing, install a new bulb | 1/3/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | No | No | the location of the 110 volt breaker for the elevator cab lights is not marked down in the machine room, could not find breaker for the lights | 1/3/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | machine room fire extinguisher inspection tag is from 2020, have the fire extinguisher inspected and tagged annually | 10/27/2025 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)8 | No | No | could not find the 110 volt breaker for the elevator cab lights, could not test emergency lights and alarm on battery power | 10/27/2025 |