Inspection
Inspection Details
Equipment ID
26824
26824
Inspection Date
9/12/2024
9/12/2024
Inspection Type
New Installation
New Installation
Inspector Name
Rhonda Rosson
Rhonda Rosson
Mechanic Name
Jacob Williams
Jacob Williams
Relief Valve Pressure
Slide
16.5
16.5
Governor Rope Pull
35/210
35/210
Door Closing Force
20
20
External ID
0ef594dc-4152-4d9c-bc4d-b41f979e02e1
0ef594dc-4152-4d9c-bc4d-b41f979e02e1
Location
Vande East Apartments
214 S Vandeventer, St Louis, MO
Phone: (000) 000-0000
Email: cbyker@arcomurray.com
214 S Vandeventer, St Louis, MO
Phone: (000) 000-0000
Email: cbyker@arcomurray.com
Owner
Attn: Director of Property Management
Vande East Partners, LLC
319 N 4th St. Suite 1000, St. Louis, MO 63102
Phone: (314) 242-1331
Email: Todd.Rogan@newandfound.com
Vande East Partners, LLC
319 N 4th St. Suite 1000, St. Louis, MO 63102
Phone: (314) 242-1331
Email: Todd.Rogan@newandfound.com
Billing
Attn: Vande East Partners
Vande East Partners
3835 Foundry Way, St. Louis, MO 63110
Phone: (314) 242-1331
Email: cbyker@arcomurray.com
Vande East Partners
3835 Foundry Way, St. Louis, MO 63110
Phone: (314) 242-1331
Email: cbyker@arcomurray.com
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.2.1(a) | No | No | A record of firefighters service operation, tested mothly as required by 8.6.11.1, with identification of the person(s) that perfomed the operation and the date shall be avaliable on site. | 8/14/2026 |
| A17.1-2016 : Elevators | 2.8 - Pipes, wiring, and ducts | 2.8.2 | No | No | Feeder location for the main and lighting branch circuits shall be marked on the disconnects. | 8/14/2026 |
| A17.1-2016 : Elevators | 2.3 - Lighting and receptacles | 2.8.2 | No | No | An electrical box cover is missing in the overhead and shall be replaced. | 8/14/2026 |
| A17.1-2016 : Elevators | 1.6 - Car emergency signal | 3.27 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | 2-WAY COMMUNICATION DEVICE SHALL WORK.Voice works, Camera works, text does not | |
| A17.1-2016 : Elevators | 5.2 - Bottom clearance, runby, and minimum refuge space | 2.4.2 | Yes | No | Counterweight runby(5") is less than required minimum of 6" | |
| A17.1-2016 : Elevators | 2.8 - Pipes, wiring, and ducts | 2.8.2 | No | No | Feeder locations for the main and lighting branch circuits shall be marked on the disconnects. | |
| A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.2.2 On-Site Documentation | No | No | A code compliant MCP and related on-site documentation shall be provided in the machine room | |
| A17.1-2016 : Elevators | 3.2 - Car top light and outlet | 8.11.2.1.3(b) | No | No | Car top work light does not work. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | No | No | A data plate, permanently and securely attached, shall be provided in the pit, in the vicinity of the Counterweight buffer indicating Maximum designed counterweight runby | |
| A17.1-2016 : Elevators | 2.3 - Lighting and receptacles | 2.8.2 | No | No | Control Space(6th Floor Lobby) shall have at least one(1) GFCI outlet. Currently no outlet. | |
| A17.1-2016 : Elevators | 2.3 - Lighting and receptacles | 2.8.2 | No | No | An electrical box cover is missing in the overhead and shall be replaced. | |
| A17.1-2016 : Elevators | 3.17 - Door and gate equipment | 8.6.4.13 | No | No | Adjust outer upthrust roller bearings for proper clearance to door hanger track.(Floors: 2 & 4) | |
| A17.1-2016 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 8.6.4.7 Cleaning of Pits | No | No | Pit shall be kept clean. Remove excess debris. |