Inspection
Inspection Details
Equipment ID
5822
5822
Inspection Date
11/19/2018
11/19/2018
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Daniel Letcher
Daniel Letcher
Mechanic Name
Daniel Novak
Daniel Novak
Relief Valve Pressure
340
340
Slide
Governor Rope Pull
Door Closing Force
24
24
External ID
bbe2a837-f3f9-4efd-91e3-99d2a57a5047
bbe2a837-f3f9-4efd-91e3-99d2a57a5047
Location
William Chrisman High School
1223 N NOLAND RD, INDEPENDENCE, MO
1223 N NOLAND RD, INDEPENDENCE, MO
Owner
Attn: Independence School District
Independence School District
201 N FOREST AVE, INDEPENDENCE, MO 64050
Phone: (000) 000-0000
Independence School District
201 N FOREST AVE, INDEPENDENCE, MO 64050
Phone: (000) 000-0000
Billing
Attn: Independence School District
Independence School District
201 N FOREST AVE, INDEPENDENCE, MO 64050
Phone: (000) 000-0000
Email: Geri_frink@isdschools.org
Independence School District
201 N FOREST AVE, INDEPENDENCE, MO 64050
Phone: (000) 000-0000
Email: Geri_frink@isdschools.org
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (S) - Fire Service | (S)1 | Yes | No | fire service phase 2 did not work at all, could not close the doors to go to other floors | 1/15/2019 |
| MO Minimum : Elevators | (S) - Fire Service | 8.6.11.1 Monthly Test and Log | No | No | Need to perform and post monthly fire service test log in the elevator machine room | 11/25/2019 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | clean the debris from pit | 2/23/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | The Maintenance Control Program (MCP) On-Site documents are not in the machine room. | 1/3/2022 |
| MO Minimum : Elevators | (S) - Fire Service | 8.6.11.1 Monthly Test and Log | No | No | The firefighters service test log is not being filled out monthly. | 1/3/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.5.7 Record of Oil Usage | No | No | could not find a oil record log in the machine room | 1/3/2022 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)6 | No | No | label the controller, disconnect, cartop, pit, and car operating panel Elevator #3 | 1/3/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | No | No | could not find the sign with directions to the location of the elevator light disconnect, could not find breaker for the 110 volt cab lights | 1/3/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | car top work light was burnt out, Replace light bulb | 1/3/2022 |
| MO Minimum : Elevators | (S) - Fire Service | 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) | Yes | No | fire service phase 1 did not work at all, turned keyswitch to on position and the elevator remained on normal operation, repair and retest fire service | 8/15/2022 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)8 | No | No | the location of the 110 volt breaker is not written down in the machine room, could not find disconnect, could not test emergency light battery system | 10/27/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | could not find Maintenance Control Program (MCP) documents in the machine room | 10/27/2025 |
| MO Minimum : Elevators | (S) - Fire Service | 8.6.11.1 Monthly Test and Log | No | No | did not find monthly fire service test log in the machine room | 10/27/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6 General Maintenance Methods | No | No | Replace burnt out car top light bulb | 10/27/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6 General Maintenance Methods | No | No | In car stop switch is broken, repair stop switch on the car operating panel and remove jumper on the controller | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Only one emergency light bulb worked, replace burnt out emergency light bulb | |
| MO Minimum : Elevators | (S) - Fire Service | 211.8 Switch Keys | No | No | Fire service key is not the same as the other two elevators, change the fire service key to the same key used on the other two elevators |