Inspection
Inspection Details
Equipment ID
20431
20431
Inspection Date
11/20/2018
11/20/2018
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Daniel Letcher
Daniel Letcher
Mechanic Name
Daniel Novak
Daniel Novak
Relief Valve Pressure
500
500
Slide
Governor Rope Pull
Door Closing Force
23
23
External ID
3ecea730-d272-4af3-abdd-d8be206b938f
3ecea730-d272-4af3-abdd-d8be206b938f
Location
Luff Elementary School
3700 S DELAWARE AVE, INDEPENDENCE, MO
3700 S DELAWARE AVE, INDEPENDENCE, MO
Owner
Attn: Independence School District
Independence School District
201 N FOREST AVE, INDEPENDENCE, MO 64050
Phone: (000) 000-0000
Independence School District
201 N FOREST AVE, INDEPENDENCE, MO 64050
Phone: (000) 000-0000
Billing
Attn: Independence School District
Independence School District
201 N FOREST AVE, INDEPENDENCE, MO 64050
Phone: (000) 000-0000
Email: Geri_frink@isdschools.org
Independence School District
201 N FOREST AVE, INDEPENDENCE, MO 64050
Phone: (000) 000-0000
Email: Geri_frink@isdschools.org
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.11.2.1.4(l) | Yes | Yes | elevator did not return to the recall floor when the phase 1 keyswitch was turned to the on position, it stayed in normal operation. reset the parameters so that fire service works. | 1/15/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.11.1 | No | No | Need to perform and post monthly fire service test log in the elevator machine room | 2/23/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | the emergency phone did not work, provide working phone line to the elevator controller | 3/12/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.7 - Fire Extinguisher | 8.6.1.6.5 | No | No | provide a ABC type fire extinguisher in or near the machine room, could not find a fire extinguisher | 2/23/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | alarm bell failed | 4/2/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.2.6 Sump Pump Covers | No | No | provide a cover for the pit sump pump. | 2/23/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | provide a record of findings for firefighters' service operation | 2/23/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | The Maintenance Control Program (MCP) On-Site documents are not in the machine room. | 1/28/2022 |
| MO Minimum : Elevators | (S) - Fire Service | 8.6.11.1 Monthly Test and Log | No | No | The firefighters service test log is not being filled out monthly. | 1/28/2022 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing | No | No | The next overspeed valve test will be in 2025 | 1/28/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | both of the car top work lights are burnt out, replace bulbs | 1/28/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | Maintenance Control Program (MCP) documents are not in the machine room | 10/27/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.5 - Housekeeping | 8.6.4.8 Machine Rooms and Machinery Spaces | No | No | Do not store non Elevator related items in the machine room | 10/27/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.7 - Fire Extinguisher | 8.6.1.6.5 | No | No | Provide Fire extinguisher in the machine room | 10/27/2025 |