Inspection
Inspection Details
Equipment ID
23429
23429
Inspection Date
8/27/2024
8/27/2024
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Sean Carmody
Sean Carmody
Mechanic Name
David Howerton
David Howerton
Relief Valve Pressure
NA
NA
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
21
21
External ID
e99d5948-6b19-4306-a50a-c510ba1b61ac
e99d5948-6b19-4306-a50a-c510ba1b61ac
Location
Zsolt Rumy Office Building
21 N Meramec Ave, Clayton, MO
Phone: (000) 000-0000
21 N Meramec Ave, Clayton, MO
Phone: (000) 000-0000
Owner
Attn: Zsolt Rumy Office Building
Zsolt Rumy Office Building
21 N Meramec Ave, Clayton, MO 63105
Phone: (000) 000-0000
Email: jschmidt@twinspringsinv.com
Zsolt Rumy Office Building
21 N Meramec Ave, Clayton, MO 63105
Phone: (000) 000-0000
Email: jschmidt@twinspringsinv.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | Display current state operating certificate. | 11/21/2019 | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.2 Design and Construction of Pits | Pit light switch shall be accessible from the pit access door. | 11/21/2019 | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.2 Design and Construction of Pits | 2.2.5.3 - The pit light switch shall be accessible from the pit access door. | 1/25/2021 | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.42 - Earthquake Inspection and Tests (Seismic Risk Zone 2 or Greater) | 8.4.10 Emegency Operation and Signaling Devices | x | The seismic displacement switch shall be operational. | 12/14/2020 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.6 - Governor-rope tension devices | 8.11.2.1.5(g) | Subsequent to the first stop of the car following the opening of the tail switch tension switch, the car shall remain inoperative until the switch is manually reset. | 11/9/2021 | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.11 - Disconnecting Means and Control | 8.11.2.1.2(k) | The disconnect located in the machine room shall be provided with a sign to identify the location of the supply side overcurrent protective device. | 11/9/2021 | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.14 - Code data plate | 8.9 | Install a code data plate. It shall read A17.1-2004. | 11/9/2021 | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) | 11/9/2021 | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | Written evacuation procedures for elevators by authorized persons and emergency personnel shall be available on-site. | 11/9/2021 | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.6.11.1 Firefighters Emergency Operation: Monthly Testing | A record of findings for firefighters' service operation required by 8.6.11.1 with identification of the person(s) that performed the operation shall be available on-site. | 11/9/2021 | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 4.2 - Hoistway doors | 8.6.4.13 | x | Fire gibs are missing from hoistway doors. | 12/14/2022 | |
| A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.2.2 On-Site Documentation | The MCP is not being filled out. The MCP shall specify examinations, tests, cleaning, lubrication, and adjustments to applicable components at regular intervals. | 10/6/2023 |