Inspection
Inspection Details
Equipment ID
10534
10534
Inspection Date
9/6/2024
9/6/2024
Inspection Type
5 Year Annual Inspection
5 Year Annual Inspection
Inspector Name
Sean Carmody
Sean Carmody
Mechanic Name
James DeBell
James DeBell
Relief Valve Pressure
NA
NA
Slide
16.75"
16.75"
Governor Rope Pull
75/450
75/450
Door Closing Force
25
25
External ID
a64a066c-6cb1-45b8-bff6-ed7ea0e1f50b
a64a066c-6cb1-45b8-bff6-ed7ea0e1f50b
Location
Kingsbury Terrace
5655 Kingsbury Ave, St. Louis, MO
Phone: (314) 361-6628
Email: pkerns@habitat.com
5655 Kingsbury Ave, St. Louis, MO
Phone: (314) 361-6628
Email: pkerns@habitat.com
Owner
Attn: Kingsbury Terrace
St. Louis Housing Authority
5655 Kingsbury Ave, St. Louis, MO 63112
Phone: (314) 361-6628
Email: lbennett@slha.org
St. Louis Housing Authority
5655 Kingsbury Ave, St. Louis, MO 63112
Phone: (314) 361-6628
Email: lbennett@slha.org
Billing
Attn: Lucius Bennett
St. Louis Housing Authority
4451 Forest Park Ave, St. Louis, MO 63108
Phone: (618) 978-3338
Email: lbennett@slha.org
St. Louis Housing Authority
4451 Forest Park Ave, St. Louis, MO 63108
Phone: (618) 978-3338
Email: lbennett@slha.org
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | Clear car top rags dirt and dust cover | 12/20/2018 |
| conversion | conversion | n/a | No | No | No Fire service log | 12/20/2018 |
| conversion | conversion | n/a | No | No | Clean oil from brake and brake shoes | 12/20/2018 |
| conversion | conversion | n/a | No | No | No MCP | 12/20/2018 |
| MO Minimum : Elevators | (A) - Hoistways | (A)13 | No | No | A temporary construction barrier was installed in the elevator hoistway between the elevator cars. This barrier is designed for only temporary use and shall be removed from the hoistway. | 12/6/2019 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | The elevator ADA telephone inside the elevator is not working properly. Check and repair the programming of this phone for proper operation and passenger safety. | 6/11/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection) | Yes | No | The car door restrictor device shall be adjusted so that it will properly catch and restrict opening of the car doors to a maximum of 4 inches when the car is away from the landing zone. Reinspection is required. | 6/11/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone does not work. | 10/14/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Phone in elevator cab does not work. | 7/28/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | Elevator cab emergency lights do not work. Re-inspection required | 6/30/2023 |
| MO Minimum : Elevators | (L) - Wire Ropes-Hoisting, Governor and Tiller | (L)12 (Re- Inspection) | Yes | Yes | Hoist ropes are rouged and undersized, replace same. Red-tagged, Re-inspection required | 11/8/2023 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Pit needs to be cleaned | 11/8/2023 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A copy of the current state certificate shall be displayed in the machine room | 11/8/2023 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Elevator appears to have emergency power operation which needs to be tested. Re-inspection required | 11/8/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | No | No | Repair / replace leaky seals on machine | 11/8/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | Emergency light & alarm are not working. Re-inspection required | 11/8/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | Elevator cab emergency lights are not working. Re-inspection required | 11/8/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.2.1 Repair Parts | No | No | Emergency power jewel didn't illuminate when transferred to emergency power. | 10/29/2024 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be obtained and displayed in the elevator machine room. | 10/29/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone is not working. | 8/21/2025 |