Inspection
Inspection Details
Equipment ID
8654
8654
Inspection Date
9/11/2024
9/11/2024
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Kurt Zimmerman
Kurt Zimmerman
Mechanic Name
James DeBell
James DeBell
Relief Valve Pressure
na
na
Slide
na
na
Governor Rope Pull
na
na
Door Closing Force
22
22
External ID
1d77888d-2cc3-4c49-b561-5e23a281cc82
1d77888d-2cc3-4c49-b561-5e23a281cc82
Location
Clayton Corporate Park Management Company
700 Corporate Park Dr, Clayton, MO
Phone: (314) 512-2602
700 Corporate Park Dr, Clayton, MO
Phone: (314) 512-2602
Owner
Attn: Joe Langenstein
Clayton Corp Park Management Company
700 Corporate Park Dr, Clayton, MO 63105
Phone: (314) 512-2602
Email: William.j.langenstein@ehi.com
Clayton Corp Park Management Company
700 Corporate Park Dr, Clayton, MO 63105
Phone: (314) 512-2602
Email: William.j.langenstein@ehi.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) | Written maintenance control program shall be kept on site for each elevator. | 12/18/2020 | ||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.5 Code Data Plate | There is no code data plate found on the equipment to indicate the code and edition that the elevator was installed to (A17.1 1984), as used for all inspections. Provide a proper plate on the front of the controller or mainline disconnect. | 9/16/2024 | ||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6 General Maintenance Methods | On the top of the elevator cab, the cab steadier bushings have degraded and require replacement. | |||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | The counterweight hitch end has a spring that is broken in the hoistway that shall be replaced for the hoisting ropes to have an equal amount of tension. | |||
| MO Minimum : Elevators | (S) - Fire Service | 211.7 Firefighters Operations/Signage | There is no signage for Firefighters Operation by the phase I and phase II key switches. Obtain the correct signage from the building code addition that this elevator was designed to meet. | 9/16/2024 | ||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.5 Code Data Plate | There is no code data plate found on the equipment to indicate the code and edition that the elevator was installed to (A17.1 1984), as used for all inspections. Provide a proper plate on the front of the controller or mainline disconnect. | |||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | On the top of the elevator cab, the cab steadier bushings have degraded and require replacement. | |||
| MO Minimum : Elevators | (L) - Wire Ropes-Hoisting, Governor and Tiller | (L)1(A) | The counterweight hitch end has a spring that is broken in the hoistway that shall be replaced for the hoisting ropes to have an equal amount of tension. | |||
| MO Minimum : Elevators | (S) - Fire Service | 211.7 Firefighters Operations/Signage | There is no signage for Firefighters Operation by the phase I and phase I key switches. Obtain the correct signage from the building cade addition that this elevator was designed to meet. | |||
| A17.1-2016 : Elevators | 1.6 - Car emergency signal | 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | Test rescue phone for all 3 units. Must be tested at the time of final modernization. | ||
| A17.1-2016 : Elevators | 2.1 - Access to machine space | 2.7.1.1 | x | Reinstall handrail on steps going into machine room. | ||
| A17.1-2016 : Elevators | 2.3 - Lighting and receptacles | 2.8.2 | x | Outlets shall be GFCI protected. | ||
| A17.1-2016 : Elevators | 2.4 - Machine space | 2.8.1 | x | Fill smoke penetrations with approved fire rated caulking. | ||
| A17.1-2016 : Elevators | 2.7 - Fire Extinguisher | 8.6.1.6.5 | x | A proper fire extinguisher shall be provided. | ||
| A17.1-2016 : Elevators | 2.11 - Disconnecting Means and Control | 2.26.4.1 | x | Main and lighting disconnects shall have proper labeling for function and feeder locations. | ||
| A17.1-2016 : Elevators | 3.10 - Hoistway construction | 2.1 | x | Fill smoke penetrations with approved fire caulking/materials. | ||
| A17.1-2016 : Elevators | 3.12 - Pipes, wiring, and ducts | 2.8 | x | Install missing duct covers. | ||
| A17.1-2016 : Elevators | 3.17 - Door and gate equipment | 8.6.4.13 | x | 3rd floor door upthrusts shall be adjusted for proper clearance. | ||
| A17.1-2016 : Elevators | 3.12 - Pipes, wiring, and ducts | 2.8 | x | Double outlet in the pit shall be GFCI protected or removed. | ||
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | x | All FAID devices to be functionality tested at completion of #3 MOD inspection. | ||
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.10 Acceptance Inspection and Test | x | All call stations in lobby must be permanently mounted. |