Inspection
Inspection Details
Equipment ID
8007
8007
Inspection Date
8/30/2024
8/30/2024
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Cynthia "CJ" Brady
Cynthia "CJ" Brady
Mechanic Name
Thomas Suedkamp
Thomas Suedkamp
Relief Valve Pressure
NA
NA
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
21
21
External ID
12ef38ad-321e-44f2-92d4-f06c0e08d708
12ef38ad-321e-44f2-92d4-f06c0e08d708
Location
Enterprise Center
1401 Clark Ave, St. Louis, MO
Phone: (314) 589-5982
1401 Clark Ave, St. Louis, MO
Phone: (314) 589-5982
Owner
Attn: Kyle Worman
Enterprise Center
1401 Clark Ave, St. Louis, MO 63103
Phone: (314) 589-5982
Email: KWorman@enterprisecenter.com
Enterprise Center
1401 Clark Ave, St. Louis, MO 63103
Phone: (314) 589-5982
Email: KWorman@enterprisecenter.com
Billing
Attn: Mindy Wallace
Enterprise Center
1401 Clark Ave, St. Louis, MO 63103
Phone: (314) 589-5982
Email: mwallace@stlblues.com
Enterprise Center
1401 Clark Ave, St. Louis, MO 63103
Phone: (314) 589-5982
Email: mwallace@stlblues.com
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (L) - Wire Ropes-Hoisting, Governor and Tiller | (L)2 | No | No | Wire ropes are degraded beyond specifications and need to be replaced. Reinspection required within 60 days. | 9/11/2019 |
| MO Minimum : Elevators | (L) - Wire Ropes-Hoisting, Governor and Tiller | (L)12 (Re- Inspection) | Yes | No | Diameter loss due to rouging exceeds proposed criteria suspension means. | 5/6/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.8 - Pipes, wiring, and ducts | 2.8.1 | Yes | No | Machine room wiring shall be enclosed. | 10/9/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.8 - Pipes, wiring, and ducts | 2.8.1 | Yes | No | All wireway and electrical device covers shall be installed. | 10/9/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.8 - Pipes, wiring, and ducts | 2.8.1 | Yes | No | Temporary wiring shall be removed. | 10/9/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.3 - Lighting and receptacles | 2.7.5.1 | Yes | No | The machine room light bulbs shall be guarded. | 10/9/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.3 - Lighting and receptacles | 8.11.2.1.2(c) | Yes | No | Provide at least one GFCI duplex receptacle in the machine room. | 10/9/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.7 - Fire Extinguisher | 8.11.2.1.2(g) | Yes | No | Provide a current ABC type fire extinguisher in the machine room. | 10/9/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 4.8 - Hoistway enclosure | 2.1.1 | Yes | No | The penetrations in the hoistway shall be sealed. | 10/9/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.4 - Machine space | 2.7.2.1 | Yes | No | Equipment in the machine room not being used in conjunction with the function or use of the elevator shall be removed. | 10/9/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.10 - Numbering of elevators, machines, and disconnect switches | 2.26.4 | Yes | No | The main disconnects shall have feeder locations labeled. | 10/9/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.2 - Bottom clearance, runby, and minimum refuge space | 2.4.1 | Yes | No | 2.4.5 - A counterweight runby sign shall be installed in the pit. | 10/9/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 2.27.2 | Yes | No | A standby power test shall be performed. | 10/9/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.20 - Governor rope | 2.18.5 | Yes | No | A governor rope tag shall be installed. | 10/9/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.2.5 Sump pump shall be provided | Yes | No | 2.2.2.6 - The sump pump cover shall be level with the pit floor. | 10/9/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.15 - sign and operating device symbols | 2.26.12 | Yes | No | A sign shall be posted adjacent to the hall call fixtures at each floor instructing occupants not to use the elevator in case of a fire. The sign shall include only the wording and graphics shown in Fig. 2.27.9 of A17.1-2005. | 10/9/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.11 - Disconnecting Means and Control | 2.26.4 | Yes | No | The car lighting branch circuit shall be separate and shall not feed the hall button riser power supply. | 10/9/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.11 Runby (Re-Inspection) | Yes | No | Provide minimum c/w run by. | 8/2/2022 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Expired | 2/15/2023 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 3/31/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.2 - Bottom clearance, runby, and minimum refuge space | 2.4.2 | Yes | No | Counterweight runby(4.5") does not meet the Code required minimum allowable Runby to prevent potential Traction Loss. Ropes need to be shortened. | 5/1/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.1 - Access to machine space | 2.7.3.4 | No | No | Machine room door shall be self-closing and self-locking . Latch is jammed and does not prevent entry. | 5/1/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 5/1/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.1 - Access to machine space | 2.7.3.4 | No | No | Machine room door shall be self-closing and self-locking . Latch is jammed and does not prevent entry |