Inspection
Inspection Details
Equipment ID
6304
6304
Inspection Date
8/29/2024
8/29/2024
Inspection Type
5 Year Annual Inspection
5 Year Annual Inspection
Inspector Name
Kevin Hecht
Kevin Hecht
Mechanic Name
Jarod Watson
Jarod Watson
Relief Valve Pressure
NA
NA
Slide
18"
18"
Governor Rope Pull
TBD
TBD
Door Closing Force
TBD
TBD
External ID
eeef7274-f883-4d23-90ba-fd8f7b9e4dd2
eeef7274-f883-4d23-90ba-fd8f7b9e4dd2
Location
Witte Bldg
707 N 2nd St, St. Louis, MO
Phone: (314) 241-1918
Email: pat.travers@druryhotels.com
707 N 2nd St, St. Louis, MO
Phone: (314) 241-1918
Email: pat.travers@druryhotels.com
Owner
Attn: Drury Development Corp- Witte Bldg
Drury Development Corp- Witte Bldg
13075 Manchester Road Suite 200, St. Louis, MO 63141
Phone: (314) 423-6698
Alt Phone: (314) 587-2552
Email: ap@drurydevelopment.com
Drury Development Corp- Witte Bldg
13075 Manchester Road Suite 200, St. Louis, MO 63141
Phone: (314) 423-6698
Alt Phone: (314) 587-2552
Email: ap@drurydevelopment.com
Billing
Same as Owner
Violations
Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
---|---|---|---|---|---|---|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.11 - Disconnecting Means and Control | 2.26.4 | x | Provide feeder location on 110v disconnect. | 3/11/2020 | |
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.2 Design and Construction of Pits | x | Provide a code compliant pit ladder. Current ladder does not comply with Missouri Minimums. | 3/11/2020 | |
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.5 Illumination of Pits | x | Provide code compliant pit lighting, measured at 7 ftc. | 3/11/2020 | |
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.2 Design and Construction of Pits | x | Provide means to reset GFCI receptacle in the pit. | 3/11/2020 | |
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.10 - Hoistway construction | 8.11.2.1.3(p) | x | Seal all holes and penetrations in the hoistway. | 3/11/2020 | |
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.15 - sign and operating device symbols | 8.11.2.1.1(o) | x | Provide missing lobby warning placard on 6th floor. | 3/11/2020 | |
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.3 - Lighting and receptacles | 8.11.2.1.2(c) | x | Provide GFCI type receptacle in the elevator machine room. | 3/11/2020 | |
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.7 - Fire Extinguisher | 8.11.2.1.2(g) | x | Provide a fire extinguisher in the elevator machine room mounted in a readily accessible location. | 3/11/2020 | |
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.11 - Disconnecting Means and Control | 2.26.4 | x | Provide feeder location on main line disconnect. | 3/11/2020 | |
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | A current MO State operating certificate shall be obtained and displayed in the elevator machine room. | 11/3/2023 | ||
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 4.2 - Hoistway doors | 8.6.4.13 | x | There are fire gibs missing from the hoistway doors. | 8/21/2023 | |
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 4.2 - Hoistway doors | 8.6.4.13 | x | There are fire gibs missing from the hoistway doors. (2nd Notice) | 9/19/2023 | |
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | MCP, including PM records and monthly fire service log, not being properly documented. | |||
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.23 - Suspension rope | 2.20 | Suspension rope tail ends shall be properly seized/banded. (Currently just electrical taped, multiple ends missing) | |||
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 4.2 - Hoistway doors | 8.6.4.13 | x | Hoistway door safety retainers missing on all floors. | ||
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) | A current MCP and related maintenance records, including fire service log, shall be on-site. | |||
MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | x | Remainder of inspection shall be completed: Remaining category 5 testing/annual items: Car and counterweight buffers, door pressure, final limit switch, and governor pull out/pull thru. |