Inspection
Inspection Details
Equipment ID
19445
19445
Inspection Date
10/30/2018
10/30/2018
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Michael Ledden
Michael Ledden
Mechanic Name
David Howerton
David Howerton
Relief Valve Pressure
490
490
Slide
Governor Rope Pull
Door Closing Force
21
21
External ID
2f0949ab-f75f-49f8-b342-85e19120b745
2f0949ab-f75f-49f8-b342-85e19120b745
Location
Oberon, LLC
4171 CRESCENT DR, SAINT LOUIS, MO
4171 CRESCENT DR, SAINT LOUIS, MO
Owner
DLJ Properties LLC
3494 JEFFCO BLVD, ARNOLD, MO 63010-3919
3494 JEFFCO BLVD, ARNOLD, MO 63010-3919
Billing
Attn: DLJ Properties LLC
3494 JEFFCO BLVD, ARNOLD, MO 63010-3919
3494 JEFFCO BLVD, ARNOLD, MO 63010-3919
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-1996 : Elevators | 3.3 - Top-of-car operating device | 1001.2(c)(3) | No | No | Car top inspection station shall work. | 6/18/2019 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Phone in elevator cab does not work. | 6/6/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing | No | No | OSV not sealed. Perform OSV test on or before next annual inspection. | 11/2/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Display current operating certificate in machine room. | 11/2/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | the emergency phone shall be answered 24/7, this phone is calling 911, and they are unable to communicate with passengers in elevator. | 4/10/2023 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A copy of the current state operating certificate shall be displayed in the machine room | 4/22/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.5 - Housekeeping | 8.6.4.8 Machine Rooms and Machinery Spaces | No | No | Remove any non elevator related equipment from the elevator machine room | 4/22/2024 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)1 | No | No | Provide machine room door to be self locking type ( no button). | |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)1 | No | No | Remove all non elevator related items from the elevator machine room. | |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | Seal hole in machine room wall. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | Provide current year tested fire extinguisher in the elevator machine room. |