Inspection
Inspection Details
Equipment ID
4104
4104
Inspection Date
8/26/2024
8/26/2024
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Steven Salabay
Steven Salabay
Mechanic Name
James DeBell
James DeBell
Relief Valve Pressure
NA
NA
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
24
24
External ID
293212e3-5d40-45a9-96a2-ef4652c77b5c
293212e3-5d40-45a9-96a2-ef4652c77b5c
Location
Renaissance Hotel (9th & St. Charles Garage)
419 N 9th St, St. Louis, MO
Phone: (314) 621-4221
419 N 9th St, St. Louis, MO
Phone: (314) 621-4221
Owner
Attn: MO Development Finance Board
MO Development Finance Board
PO Box 567, Jefferson City, MO 65102
Phone: (314) 241-7777 Ext: 112
MO Development Finance Board
PO Box 567, Jefferson City, MO 65102
Phone: (314) 241-7777 Ext: 112
Billing
Attn: Kenny Darragh
St. Louis Parking Company
1617 S 3rd, St. Louis, MO 63104
Phone: (314) 456-5664
Email: kennyd@stlouisparking.com
St. Louis Parking Company
1617 S 3rd, St. Louis, MO 63104
Phone: (314) 456-5664
Email: kennyd@stlouisparking.com
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | conversion - reinspect | Yes | No | Emergency phone not working due to bad phone line. Reinspect. | 8/23/2018 |
| A17.1-1996 : Elevators | 3.1 - Top-of-car stop switch | 1001.2(c)(1) | No | No | Replace broken stop switch on elevator car top. | 11/4/2020 |
| A17.1-1996 : Elevators | 2.7 - Fire Extinguisher | 1206.1h | No | No | Update fire extinguisher in machine room | 12/21/2022 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 11/10/2022 |
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 1206.7 | No | No | A record of findings for firefighters' service operation required by 8.6.11.1 with identification of the person(s) that performed the operation shall be kept on site. | 11/10/2022 |
| A17.1-1996 : Elevators | 2.7 - Fire Extinguisher | 1206.1h | No | No | An ABC fire extinguisher with a current test tag shall be mounted convenient to the machine room door. | 11/10/2022 |
| A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | The MCP, including PM records and monthly fire service test log are not being properly documented. | 2/24/2026 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Two-way communication device shall give proper location, message, full address & unit number. | 9/28/2023 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Testing incomplete. Fire service, Phase 1 & 2 need to be tested. | 9/28/2023 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Testing incomplete. Fire service, Phase 1 & 2 need to be tested. | 8/26/2024 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency communication/phone in car is not working. | 10/3/2024 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 2/24/2026 |
| A17.1-1996 : Elevators | 3.23 - Suspension rope | 212 | Yes | No | Hoisting ropes failed gauge test, need to be replaced. | 10/3/2024 |