Inspection
Inspection Details
Equipment ID
20940
20940
Inspection Date
10/26/2017
10/26/2017
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Unknown Conversion
Unknown Conversion
Mechanic Name
Relief Valve Pressure
Slide
10"
10"
Governor Rope Pull
35/500
35/500
Door Closing Force
16
16
External ID
Location
Metropolitan Artists Lofts
500 N Grand, St. Louis, MO
Phone: (314) 713-5278
500 N Grand, St. Louis, MO
Phone: (314) 713-5278
Owner
Metropolitan Artists Lofts
500 N Grand, St. Louis, MO 63103
500 N Grand, St. Louis, MO 63103
Billing
Attn: Metropolitan Artists Lofts
500 N Grand, , MO 63103
500 N Grand, , MO 63103
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | Emergency lights shall work | 12/9/2019 |
| A17.1-2016 : Elevators | 3.23 - Suspension Means | 8.6.3.2 (Re-Inspection) | Yes | No | Suspension ropes are undersized and rouged, need to be replaced. Re-inspection required | 2/13/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.2.1 Repair Parts | No | No | The “smoke guard” barrier device, that was installed on a number of hoistway door landings, has been activated and not reset properly. The device has been temporarily wrapped up rendering it inoperable in case of an actual emergency. Repair and reset all “smoke guard” barrier devices to operate as designed. | 2/3/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.18 - Restricted opening of car or hoistway doors | 2.12.5 Restricted Opening of Hoistway or Car Doors (Re-Inspection) | Yes | No | The car door restrictor device shall be adjusted so that it will properly catch and restrict opening of the car doors to a maximum of 4 inches when the car is away from the landing zone. Reinspection is required. | 2/3/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.16 - Traveling cables and junction boxes | 2.8.1 | No | No | The car traveling cable, underneath the car, is cracked through the outer insulation as the car reaches the lobby. Confirm that no internal wires have been affected and repair or replace traveling cable. | 2/3/2026 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | The testing has not been completed on the elevator at this time. The emergency power testing, door pressure, and unintended motion test before the inspection is completed. | 2/3/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.2.1 Repair Parts | No | No | Smoke guard barrier on floor 3 is rolled up and on top of enclosure. Barrier shall be repaired so that it will work in case of emergency. | 2/25/2026 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 2.27.2 | Yes | No | Elevator is not transferring to generator power when the generator transfer switch is activated. Repair and reinspect. | 2/25/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.2.1 Repair Parts | No | No | Smoke guard barrier on floor 3 is rolled up and on top of enclosure. Barrier shall be repaired so that it will work in case of emergency. |