Inspection
Inspection Details
Equipment ID
24345
24345
Inspection Date
9/12/2024
9/12/2024
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Cynthia "CJ" Brady
Cynthia "CJ" Brady
Mechanic Name
James Bishop
James Bishop
Relief Valve Pressure
320
320
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
17
17
External ID
a0484e58-1ac2-415a-803b-d1ab547db0d6
a0484e58-1ac2-415a-803b-d1ab547db0d6
Location
Concordia House
111 E Woodbine Ave, Kirkwood, MO
Phone: (314) 822-7771
111 E Woodbine Ave, Kirkwood, MO
Phone: (314) 822-7771
Owner
Attn: Concordia House
Concordia House
111 E Woodbine Ave, Kirkwood, MO 63122
Phone: (314) 822-7771
Email: concordiahouse@yahoo.com
Concordia House
111 E Woodbine Ave, Kirkwood, MO 63122
Phone: (314) 822-7771
Email: concordiahouse@yahoo.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-2016 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 8.6.4.7 Cleaning of Pits | No | No | Remove water and mold from the pit. | 12/16/2021 |
| A17.1-2016 : Elevators | 2.39 - Low Oil Protection | 8.6.5.14.3(i) | No | No | A written record shall be kept of the quantity of hydraulic fluid added to the system and emptied from leakage collection containers and pans, shall not exceed 5 gal before removal, shall be covered, and shall not be permitted to overflow. Note: Per the State of Missouri AHJ: "The use of oil recovery systems to return the hydraulic fluid back into the main reservoir by automatic means or by gravity feed prevents proper monitoring of the gland packing and seals", and "machine rooms cannot be used as containment areas". | 12/16/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing | No | No | This elevator is equipped with an overspeed valve. Based on the installation date of 2018, a category 5 test shall be performed on the overspeed valve in 2023. The valve shall be sealed and tagged after the category 5 test. | 10/19/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 3.27 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The in car emergency telephone shall be operational. | 10/19/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 10/19/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 3.27 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The in car emergency alarm bell shall be operational, with and without main power. | 10/31/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.18 - Restricted opening of car or hoistway doors | 2.12.5 Restricted Opening of Hoistway or Car Doors (Re-Inspection) | Yes | No | Means to restrict car doors is not functional. Take corrective action and re-test. | 2/17/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 3.26.10 (Auxiliary Power)(Re-Inspection) | Yes | No | Auxiliary power lowering operation is not functional. | 2/17/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 3.26.10 (Auxiliary Power)(Re-Inspection) | Yes | No | Auxiliary power lowering was tested and is still not functional. | 4/6/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.18 - Restricted opening of car or hoistway doors | 2.12.5 Restricted Opening of Hoistway or Car Doors (Re-Inspection) | Yes | No | Means to restrict car doors are stil not fuctional. | 4/6/2026 |