Inspection
Inspection Details
Equipment ID
14320
14320
Inspection Date
9/12/2024
9/12/2024
Inspection Type
Reinspection
Reinspection
Inspector Name
Robert Kehm
Robert Kehm
Mechanic Name
Richard Hawkins
Richard Hawkins
Relief Valve Pressure
NA
NA
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
NA
NA
External ID
6db04d9c-5909-49e5-a6d7-01ce44f893be
6db04d9c-5909-49e5-a6d7-01ce44f893be
Location
St. Louis Hills Assisted Living & Memory Care
6543 Chippewa St, St. Louis, MO
Phone: (314) 647-6600
6543 Chippewa St, St. Louis, MO
Phone: (314) 647-6600
Owner
Attn: Heather Schmidt
St. Louis Hills Assisted Living & Memory Care
6543 Chippewa St, St. Louis, MO 63109
Phone: (314) 647-6600
Email: heather@stlhillsliving.com
St. Louis Hills Assisted Living & Memory Care
6543 Chippewa St, St. Louis, MO 63109
Phone: (314) 647-6600
Email: heather@stlhillsliving.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | conversion - reinspect | Yes | No | Phase 2 fire service does not work properly. Car call lock out shall be bypassed while on Phase 2 emergency fire service. | 12/18/2018 |
| MO Minimum : Elevators | (S) - Fire Service | (S)1 | Yes | No | Test all heat & smoke devices. | 12/19/2018 |
| MO Minimum : Elevators | (I) - Pits | (I)8 | Yes | No | Repair or replace the pit sump pump. | 12/19/2018 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.2 Design and Construction of Pits | No | No | Pit sump pump needs to be replaced and the discharge line needs to be made of a non-combustible material. | 3/18/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Display a copy of the current state operating certificate. | 3/18/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO state operating certificate shall be posted in the elevator machine room. | 12/15/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The in car emergency telephone shall be operational. | 1/11/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. Evacuation procedures are missing. (This item is for notification purposes for future violation in 2022) | 11/16/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | The in car emergency bell shall be operational. | 1/18/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | The in car emergency light shall be operational. | 1/18/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | An ABC fire extinguisher with a current test tag shall be mounted in the machine room located convenient to the access door. | 2/10/2026 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 2/10/2026 |
| MO Minimum : Elevators | (S) - Fire Service | 8.6.11.1 Monthly Test and Log | No | No | Fire service log shall be updated monthly. | 2/10/2026 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | There is water in the pit; take corrective action as needed. | 2/10/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.17 - Drive machine brake | 8.6.4.19.11 A17.1 2016 Ascending Overspeed Protection, Unintended Movement Devices, and Emg Brake | Yes | Yes | Emergency brake (rope gripper) is not functional. Elevator Red Tagged and removed from service. | 9/12/2024 |