Inspection
Inspection Details
Equipment ID
10515
10515
Inspection Date
9/17/2024
9/17/2024
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Cynthia "CJ" Brady
Cynthia "CJ" Brady
Mechanic Name
Peter Buchan
Peter Buchan
Relief Valve Pressure
TBD
TBD
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
14
14
External ID
ae343d18-60a6-4a48-ad23-d46042d3249c
ae343d18-60a6-4a48-ad23-d46042d3249c
Location
Mark Shale
1147 Saint Louis Galleria, Clayton, MO
Phone: (314) 725-4888
1147 Saint Louis Galleria, Clayton, MO
Phone: (314) 725-4888
Owner
Attn: Mary Brod
General Growth Properties
1155 Saint Louis Galleria, St. Louis, MO 63117
Phone: (314) 571-7006
Email: mary.brod@bpretail.com
General Growth Properties
1155 Saint Louis Galleria, St. Louis, MO 63117
Phone: (314) 571-7006
Email: mary.brod@bpretail.com
Billing
Attn: General Growth Properties
General Growth Properties
1155 Saint Louis Galleria, St. Louis, MO 63117
Phone: (314) 571-7006
Email: SLGinfo@bpretail.com
General Growth Properties
1155 Saint Louis Galleria, St. Louis, MO 63117
Phone: (314) 571-7006
Email: SLGinfo@bpretail.com
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | Replace pit light. | 1/14/2021 | ||
| MO Minimum : Elevators | (I) - Pits | (I)1 | Clean pit. | 1/14/2021 | ||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection) | x | Car door restrictor shall work through-out hoistway. | 9/17/2024 | |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | x | 2-way communication device very staticy per agent, could not understand most of our speech. | 9/17/2024 | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13 - Door systems | Adjust up-thrust roller bearings for proper clearance to door hanger track. (Multiple floors) | 5/21/2025 | ||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) | A code compliant MCP and related on-site documentation shall be provided. Note: No oil or fire service log for 2022 or 2023. | 5/21/2025 | ||
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | Current state operating permit shall be displayed. | 5/21/2025 | ||
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)8 Car Lighting | All car lamps shall work. | 5/21/2025 | ||
| MO Minimum : Elevators | (H) - Machine Rooms | (H)5 (Machine Room Lighting) | Machine room lighting needs to be repaired, 1 or more bulbs not working. | 5/21/2025 | ||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | Replace missing "Do not use elevator in case of fire" signage on multiple floors. | 5/21/2025 | ||
| MO Minimum : Elevators | (S) - Fire Service | (S)1 | x | x | Elevator will not go into Phase 2 fire service. Elevator Red Tagged. Must be corrected before red tag is removed. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.2.2(d) On-Site Documentation (Written Procedures for Evacuation and Cleaning) | Evacuation procedures are missing from the MCP. | 5/21/2025 | ||
| MO Minimum : Elevators | (S) - Fire Service | 8.6.11.1 Monthly Test and Log | Fire service testing log is missing from the MCP. | 5/21/2025 | ||
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (1) Minimum Standard | x | x | Car did not pass the 15 minute standing test. Elevator Red Tagged. | |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | x | Relief pressure shall be tested and documented. |