Inspection
Inspection Details
Equipment ID
10603
10603
Inspection Date
10/2/2024
10/2/2024
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Bradley Rasnake
Bradley Rasnake
Mechanic Name
Justin Scherer
Justin Scherer
Relief Valve Pressure
Na
Na
Slide
Na
Na
Governor Rope Pull
Na
Na
Door Closing Force
24
24
External ID
650d8fdc-d17c-4862-8fdd-7fcbbf75db55
650d8fdc-d17c-4862-8fdd-7fcbbf75db55
Location
Anheuser Busch- Bldg #202
1 Busch Pl, St. Louis, MO
Phone: (314) 577-2667
1 Busch Pl, St. Louis, MO
Phone: (314) 577-2667
Owner
Attn: 137-2
Anheuser Busch
1 Busch Pl, St. Louis, MO 63118
Phone: (314) 577-3998
Email: ryan.brohammer@anheuser-busch.com
Anheuser Busch
1 Busch Pl, St. Louis, MO 63118
Phone: (314) 577-3998
Email: ryan.brohammer@anheuser-busch.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Rear alarm bell button does not work | 10/15/2021 |
| A17.1-1996 : Elevators | 3.23 - Suspension rope | 1001.2(c)(29) | Yes | No | Suspension ropes are undersized and stretched. Reinspect in 120 days | 10/15/2021 |
| A17.1-1996 : Elevators | 3.10 - Hoistway construction | 1001.2(c)(16) | No | No | Patch holes by car doors inside hoistway | 9/19/2025 |
| A17.1-1996 : Elevators | 1.12 - Car enclosure | 1001.2(a)(12) | No | No | Cover hole on top of car with exposed wires | 9/19/2025 |
| A17.1-1996 : Elevators | 3.23 - Suspension rope | 1001.2(c)(29) | Yes | No | Suspension ropes are undersized and stretched. Reinspect in 90 days | 5/19/2022 |
| A17.1-1996 : Elevators | 3.10 - Hoistway construction | 1001.2(c)(16) | No | No | Patch holes by car doors inside hoistway | 9/19/2025 |
| A17.1-1996 : Elevators | 1.12 - Car enclosure | 1001.2(a)(12) | No | No | Cover hole on top of car with exposed wires | 9/19/2025 |
| A17.1-1996 : Elevators | 3.23 - Suspension rope | 212 | Yes | No | Suspension ropes are undersized & stretched. Re-inspection required | 10/21/2022 |
| A17.1-1996 : Elevators | 3.10 - Hoistway construction | 100 | No | No | Patch holes by car doors inside hoistway | 9/19/2025 |
| A17.1-1996 : Elevators | 2.12 - Controller Wiring, Fuses, Grounding, Etc. | 102.1 | No | No | Cover hole on top of car top with exposed wires | 9/19/2025 |
| A17.1-1996 : Elevators | 1.18 - Restricted opening of car or hoistway doors | 111.5 Restricted Opening of Hall/Car Doors | Yes | No | Car door restrictor is not working. Re-inspection required | 10/2/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13 - Door systems | No | No | The sill plate on the 2nd floor shall be replaced or repaired, there is only one anchor securing it to the floor and it is loose. | 9/19/2025 |