Inspection
Inspection Details
Equipment ID
21724
21724
Inspection Date
10/1/2024
10/1/2024
Inspection Type
Reinspection
Reinspection
Inspector Name
Michael Gallaher
Michael Gallaher
Mechanic Name
Relief Valve Pressure
Na
Na
Slide
Na
Na
Governor Rope Pull
Na
Na
Door Closing Force
Na
Na
External ID
1a4d9851-70fe-4c61-b677-66cebb0a8a3b
1a4d9851-70fe-4c61-b677-66cebb0a8a3b
Location
River City Casino Hotel
777 River City Casino Blvd, St. Louis, MO
Phone: (314) 915-7836
777 River City Casino Blvd, St. Louis, MO
Phone: (314) 915-7836
Owner
Attn: River City Hotel
PNK (River City) LLC
777 River City Casino Blvd, St. Louis, MO 63125
Phone: (314) 681-9894
Email: Charles.sheard@pngaming.com
PNK (River City) LLC
777 River City Casino Blvd, St. Louis, MO 63125
Phone: (314) 681-9894
Email: Charles.sheard@pngaming.com
Billing
Attn: River City Hotel
PNK (River City) LLC
777 River City Casino Blvd, St. Louis, MO 63125
Phone: (314) 681-9894
Email: coupainvoicing@pngaming.com
PNK (River City) LLC
777 River City Casino Blvd, St. Louis, MO 63125
Phone: (314) 681-9894
Email: coupainvoicing@pngaming.com
Violations
Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
---|---|---|---|---|---|---|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | Emergency phone does not call out. | 6/15/2022 | |
MO Minimum : Elevators | (L) - Wire Ropes-Hoisting, Governor and Tiller | (L)12 (Re- Inspection) | x | x | Coated steel belt monitor fault code says to replace belts immediatly. Replace coated steel belts. Red-tagged, Re-inspection required | 9/14/2022 |
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | Phone in elevator cab does not work, line problem. Re-inspection required | 9/14/2022 | |
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | The elevator ADA telephone inside the elevator is not operating correctly. Check and repair the programming of this phone for proper operation and passenger safety. Reinspection required in 14 days. | 4/3/2024 | |
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.3 - Lighting and receptacles | 2.7.5.1 Lighting | The lighting in the machine space overhead failed to operate on the day of testing. The lighting shall be repaired for maintenance and emergency personnel. | |||
MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | x | Elevator appears to have emergency generator backup power operation, which needs to be tested to complete inspection. Re-inspection required | 5/22/2024 | |
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | The elevator ADA telephone inside the elevator is not working correctly. Check and repair the programming of this phone for proper operation and passenger safety. Re-inspection required | 5/22/2024 | |
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.3 - Lighting and receptacles | 2.7.5.1 Lighting | The lighting in the machine space overhead failed to operate on the day of testing. The lighting shall be repaired for maintenance and emergency personnel | |||
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | The elevator ADA telephone inside the elevator is not operating correctly, check & repair the programming of this phone for proper operation and passenger safety. Re-inspection required | 5/21/2024 | |
A17.1-2016 : Elevators | 2.3 - Lighting and receptacles | 2.8.2 | The lighting in the machine space overhead failed to operate on the day of testing, needs to be repaired | |||
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | The elevator ADA telephone inside the elevator is not operating correctly. Check & repair the programming of this phone for proper operation and passenger safety. Re-inspection required | 10/1/2024 | |
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.3 - Lighting and receptacles | 2.7.5.1 Lighting | The lighting in the machine space overhead failed to operate on the day of testing. The lighting shall be repaired for maintenance & emergency personnel. |