Inspection
Inspection Details
Equipment ID
21377
21377
Inspection Date
10/3/2024
10/3/2024
Inspection Type
5 Year Annual Inspection
5 Year Annual Inspection
Inspector Name
Michael Ledden
Michael Ledden
Mechanic Name
Steven Himmelmann
Steven Himmelmann
Relief Valve Pressure
NA
NA
Slide
Wind Up
Wind Up
Governor Rope Pull
200/NA
200/NA
Door Closing Force
NA
NA
External ID
8569b64a-8b6f-43d6-8c6b-bf6607f7dd4d
8569b64a-8b6f-43d6-8c6b-bf6607f7dd4d
Location
Chemline Inc
5151 NATURAL BRIDGE AVE, SAINT LOUIS, MO
Phone: (314) 664-2230
5151 NATURAL BRIDGE AVE, SAINT LOUIS, MO
Phone: (314) 664-2230
Owner
Attn: Kenny Baum
Chemline Inc
5151 Natural Bridge Ave, St. Louis, MO 63115
Phone: (314) 664-2230 Ext: 145
Alt Phone: (314) 254-2705
Email: kbaum@chemline.net
Chemline Inc
5151 Natural Bridge Ave, St. Louis, MO 63115
Phone: (314) 664-2230 Ext: 145
Alt Phone: (314) 254-2705
Email: kbaum@chemline.net
Billing
Same as Owner
Violations
Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
---|---|---|---|---|---|---|
conversion | conversion | n/a | Replace electrical conduit on side of car | 7/25/2018 | ||
conversion | conversion | n/a | Cover junction box on car top | 7/25/2018 | ||
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | Fire extinguisher needs to be serviced. | 12/11/2018 | ||
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | Provide a current tested fire extinguisher in the elevator machine room. | 3/8/2022 | ||
MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | The machine room door shall be self-closing and self-locking. | 3/8/2022 | ||
MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | A permanent lighting fixture shall be provided in all pits to provide illumination of not less then 5 ftc at the pit floor. | 3/8/2022 | ||
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | Provide a code compliant MCP including onsite documents. | 3/8/2022 | ||
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. Evacuation procedures are missing. (This item is for notification purposes for future violation in 2022) | 3/7/2022 | ||
MO Minimum : Elevators | (M) - Car Safeties and Speed Governors | (M)4 | x | x | The movement of the safety drum rope, starting from a fully retracted position, must not exceed 42 inches (it pulled out approximately 120 inches) before the safety shoes contact the rail. Elevator Red Tagged. | 10/10/2022 |
MO Minimum : Elevators | (I) - Pits | (I)1 | Water and oil shall not be allowed to accumulate on the pit floors. Note: The pit floor is covered with several inches of water. | 3/14/2023 | ||
MO Minimum : Elevators | (A) - Hoistways | (A)16 | All electrical wiring in the hoistway shall be enclosed in metal conduit, flexible conduit, metal raceway, or be in compliance with NFPA70. Note: There are bare wires running throughout the hoistway. | 3/14/2023 | ||
MO Minimum : Elevators | (A) - Hoistways | (A)16 | The missing junction box covers in the hoistway shall be replaced. | 3/14/2023 | ||
MO Minimum : Elevators | (A) - Hoistways | (A)12 | The penetrations in the hoistway shall be sealed with approved materials. | 3/14/2023 | ||
MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | The fluorescent pit light shall be operational and permanently wired. Note: The fixture is currently attached to a cord which runs through a hole in the hoistway wall and is plugged into an extension cord. | 3/14/2023 | ||
MO Minimum : Elevators | (C) - Car Enclosure: Freight | (C)5 | Properly secure cab lights to ceiling. |