Inspection
Inspection Details
Equipment ID
10131
10131
Inspection Date
10/7/2024
10/7/2024
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Jerry Eckhart
Jerry Eckhart
Mechanic Name
Christian Schickedanz
Christian Schickedanz
Relief Valve Pressure
750
750
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
18
18
External ID
e6fcac9b-0788-49f4-923e-e542e6fc466a
e6fcac9b-0788-49f4-923e-e542e6fc466a
Location
Life Storage
6557 Manchester Ave, St. Louis, MO
Phone: (314) 646-1107
Email: elevators@lifestorage.com
6557 Manchester Ave, St. Louis, MO
Phone: (314) 646-1107
Email: elevators@lifestorage.com
Owner
Attn: Life Storage
Extra Space Management, Inc
2795 E. Cottonwood Pkwy #400, Salt Lake City, UT 84121
Phone: (716) 650-6139
Fax: (716) 810-8130
Email: fac3219@extraspace.com
Extra Space Management, Inc
2795 E. Cottonwood Pkwy #400, Salt Lake City, UT 84121
Phone: (716) 650-6139
Fax: (716) 810-8130
Email: fac3219@extraspace.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone does not work. | 2/9/2021 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing | No | No | OSV is not sealed and must have a cat 5 weight test performed | 12/1/2021 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)5 (Machine Room Lighting) | No | No | Provide existing machine room lights to work. | 2/19/2026 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)4 | No | No | Remove all non elevator related items from the elevator machine room. | 2/19/2026 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Provide existing battery backup lowering unit to work properly. | 10/7/2024 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current State Elevator Certificate. | 2/19/2026 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 3.26.10 | Yes | No | Repair inoperative ERU device | 2/19/2026 |
| A17.1-2016 : Elevators | 2.7 - Fire Extinguisher | 8.6.1.6.5 | No | No | Supply up to date serviced fire extinguisher | 2/19/2026 |
| A17.1-2016 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 3.27.1 Phase I Emergency Recall Operation After Device Actuation | Yes | Yes | Car emergency stop switch not overridden | 2/19/2026 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | Yes | No | Provide existing battery backup lowering unit (ERU) to work properly. | |
| A17.1-2016 : Elevators | 2.7 - Fire Extinguisher | 8.6.1.6.5 | No | No | Provide current year tested fire extinguisher in the elevator machine room. | |
| A17.1-2016 : Elevators | 1.5 - Car lighting and receptacles | 8.6.4.15 Car Emergency System (Re-Inspection) | Yes | No | Provide existing emergency lights and bell to work. |