Inspection
Inspection Details
Equipment ID
16346
16346
Inspection Date
10/10/2024
10/10/2024
Inspection Type
Reinspection
Reinspection
Inspector Name
Jerry Eckhart
Jerry Eckhart
Mechanic Name
Christopher Davis
Christopher Davis
Relief Valve Pressure
NA
NA
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
NA
NA
External ID
49077125-6289-449a-95c3-bd992c50eced
49077125-6289-449a-95c3-bd992c50eced
Location
MetroLink- North Hanley Parking Garage
4401 N Hanley Rd, St. Louis, MO
Phone: (314) 982-1400
4401 N Hanley Rd, St. Louis, MO
Phone: (314) 982-1400
Owner
Attn: Metro Accounts Payable
Metro Accounts Payable
707 N 1st St, St. Louis, MO 63102
Phone: (314) 982-1400
Email: eastefano@MetroStLouis.org
Metro Accounts Payable
707 N 1st St, St. Louis, MO 63102
Phone: (314) 982-1400
Email: eastefano@MetroStLouis.org
Billing
Attn: Metro Accounts Payable
Metro Accounts Payable
PO Box 1349, St. Louis, MO 63188
Phone: (314) 982-1400
Email: dxstill@MetroStLouis.org
Metro Accounts Payable
PO Box 1349, St. Louis, MO 63188
Phone: (314) 982-1400
Email: dxstill@MetroStLouis.org
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 1206.2a (Pits and Hoistways) | No | No | Sump is full of oil and unplugged. | 11/4/2020 |
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 1001.2(d)12 | Yes | No | Door open button not working properly on Phase I recall. Reinspect 14 days to repair. Phase I recalls the elevator to main floor and opens door. Door open button will not reopen door once on Phase I. | 7/2/2020 |
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 106.1e Illumination of Pits | No | No | Repair GFI receptable and light in pit. | 11/4/2020 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current State certificate in machine room | 11/4/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | Need maintenance control program on site and posted on controller | 11/4/2020 |
| MO Minimum : Elevators | (S) - Fire Service | 8.6.11.1 Monthly Test and Log | No | No | Fire service has to be tested monthly and recorded on log in machine room | 11/4/2020 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Phone in elevator cab does not work. | 10/29/2021 |
| A17.1-1996 : Elevators | 1.18 - Restricted opening of car or hoistway doors | 1001.2(a)(18) | Yes | No | Car door restrictor does not work. | 10/29/2021 |
| A17.1-1996 : Elevators | 2.32 - Control Valve | 1004.2(b)(15) | No | Yes | Performed OSV test, elevator would not lift load due to control valve failure. Red tagged elevator. | 10/29/2021 |
| A17.1-1996 : Elevators | 3.14 - Hoistway clearances | 108 | Yes | No | Clearance between the 1st floor landing sill and elevator car sill is a 1/4 inch. Clearance shall be between 1/2 inch and 1 1/2 inches. Re-inspection required | 10/10/2024 |
| A17.1-2016 : Elevators | 4.2 - Hoistway doors | 8.6.4.13 Door Systems | Yes | No | Safety retainers are missing on top and bottom hoistway doors, need to install safety retainers. Re-inspection required | 10/10/2024 |
| A17.1-2016 : Elevators | 4.2 - Hoistway doors | 8.6.4.13 Door Systems | Yes | No | Bottom floor hoistway door closing device does not work, needs repaired. Re-inspection required | 10/10/2024 |
| A17.1-1996 : Elevators | 3.14 - Hoistway clearances | 1001.2(c)(20) | Yes | No | Clearance between the 1st floor landing sill and elevator car sill is a 1/4 inch. Clearance shall be between a 1/2 inch and 1 1/2 inches. | 7/21/2025 |