Inspection
Inspection Details
Equipment ID
24143
24143
Inspection Date
10/14/2024
10/14/2024
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Thomas Krug
Thomas Krug
Mechanic Name
Kurt Warttig
Kurt Warttig
Relief Valve Pressure
Slide
na
na
Governor Rope Pull
na
na
Door Closing Force
23/24
23/24
External ID
4e576930-10ea-4e6f-9a3b-b43c09db2de0
4e576930-10ea-4e6f-9a3b-b43c09db2de0
Location
Piazza on West Pine Phase II
3940 W Pine Blvd, St. Louis, MO
Phone: (000) 000-0000
3940 W Pine Blvd, St. Louis, MO
Phone: (000) 000-0000
Owner
Attn: Piazza on West Pine
Piazza on West Pine
3939 W Pine Blvd, St. Louis, MO 63108
Phone: (000) 000-0000
Piazza on West Pine
3939 W Pine Blvd, St. Louis, MO 63108
Phone: (000) 000-0000
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.8 - Pipes, wiring, and ducts | 2.8.2 (Re-Inspection) | Yes | No | Control room illumination shall be 19 foot candles. | 8/10/2018 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.10 - Hoistway construction | 2.1 | Yes | No | Hoistway shall be as near vertical as possible. Shall be capable of holding 150#/sq ft without deformation. | 8/10/2018 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.10 - Hoistway construction | 2.1 | Yes | No | Seal all hoistway penetration to maintain fire rating. | 8/10/2018 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.12 - Pipes, wiring, and ducts | 2.8 | Yes | No | NEC Secure conduit at top of hoistway. | 8/10/2018 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.1 - Access to machine space | 2.7.1.1 | Yes | No | Install self closing, self locking door on controller disconnect room. | 8/10/2018 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.18 - Traction drive machines | 2.24 | Yes | No | Auxillary contacted on shunt and disconnect. 2.11 is not an Item Option and needs to be added. | 8/10/2018 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.17 - Drive machine brake | 2.16.8 | Yes | No | Test standby power operation. | 8/10/2018 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Telephone in car doesn't work. Will not activate | 10/22/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Telephone in car doesn't work. Phone line dead to elevator controller | 9/23/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | No | No | The emergency alarm button and door open button are missing their labels and braille. Required signs and data plates that are damaged or missing shall be repaired or replaced | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) | No | No | A written Maintenance Control Program, provided by the person(s) maintaining the equipment, shall be in place to maintain the equipment in compliance with the requirements of Section 8.6. |