Inspection
Inspection Details
Equipment ID
11317
11317
Inspection Date
10/7/2024
10/7/2024
Inspection Type
Reinspection
Reinspection
Inspector Name
Mitchell McNeely
Mitchell McNeely
Mechanic Name
Jeff Setchfield
Jeff Setchfield
Relief Valve Pressure
Na
Na
Slide
Na
Na
Governor Rope Pull
Na
Na
Door Closing Force
Na
Na
External ID
a3679aba-c491-4981-9d7b-cf89cc082e1a
a3679aba-c491-4981-9d7b-cf89cc082e1a
Location
900 N Tucker Building, LLC
900 N Tucker Blvd, St. Louis, MO
Phone: (314) 340-8754
Email: mattc@900north.biz
900 N Tucker Blvd, St. Louis, MO
Phone: (314) 340-8754
Email: mattc@900north.biz
Owner
Attn: 900 N Tucker Building, LLC
900 N Tucker Building, LLC
900 N Tucker Blvd, St. Louis, MO 63101
Phone: (314) 340-8754
Email: mattc@900north.biz
900 N Tucker Building, LLC
900 N Tucker Blvd, St. Louis, MO 63101
Phone: (314) 340-8754
Email: mattc@900north.biz
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | Provide protection for the elevator cab fan wiring. | 11/5/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)2 Alterations | No | No | Extend tape to prevent tape head from striking top bracket during buffer test. | 11/5/2020 |
| MO Minimum : Elevators | (L) - Wire Ropes-Hoisting, Governor and Tiller | (L)12 (Re- Inspection) | Yes | Yes | Governor cable pulled through jaws and did not set safeties on safety test. Red tagged elevator. | 12/1/2020 |
| MO Minimum : Elevators | (I) - Pits | (I)8 | No | No | Install sump pump to prevent the accumulation of water in the pit. | 11/5/2020 |
| MO Minimum : Elevators | (I) - Pits | (I)2 | No | No | Car buffer is full of water. | 11/5/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Program emergency phone to call a 24 hour monitoring station. | 12/1/2020 |
| MO Minimum : Elevators | (A) - Hoistways | (A)13 | No | No | Close holes at top of hoistway. | 11/5/2020 |
| MO Minimum : Elevators | (I) - Pits | (I)8 | No | No | Install pit sump pump. | 6/18/2025 |
| MO Minimum : Elevators | (A) - Hoistways | (A)16 | No | No | Enclose cab fan high voltage wiring. | 6/18/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.17 - Door and gate equipment | 2.11 | No | No | The fire tabs (Hoistway Door Safety Retainers) were not installed on the hoistway doors at the time of construction. The fire tabs shall be installed to retain the hoistway doors in the closed position if the primary means fails. | 6/18/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.3.1.6(h) Phase 2 Audible/Visual Signal (Re-Inspection) | Yes | No | The fireman's emergency service phase I and II operations was tested and the following deficiency was noted: The audible signal device did not sound when phase I was activated. Reinspection is required. | 6/25/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.9 Elevator Corridor Call Station Pictograph | No | No | The signage for “In Case of Fire Use Stairs” is not located on all landings. Install signage that conforms to the building code this elevator was installed to meet. | 6/18/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.2.1 General Maintenance Requirements Documentation | No | No | A written Maintenance Control Program (MCP) shall be in place to maintain the equipment in compliance with the requirements of 8.6.The MCP shall include but not limited to examinations, tests, cleaning, lubrication, and adjustments to applicable components at regular intervals. | 6/18/2025 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | Yes | No | This elevator has a backup emergency generator power that is used in case of a power outage. This system shall be scheduled to be tested and a reinspection is required. This requirement is due to the State of Missouri adopting the A17.1 2016 version of the elevator safety code. Reinspection required. | 6/25/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 2.27.2 | Yes | No | Provide testing of the elevator on emergency power. | 10/7/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 4.12 - Standby power selection switch | 2.27.2 | Yes | No | Provide testing of the elevator emergency power selector switch. | 10/7/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | Provide MCP. | 6/18/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current State Elevator Certificate. | 6/18/2025 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current State Elevator Certificate. | 6/18/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.18 - Restricted opening of car or hoistway doors | 2.12.5 Restricted Opening of Hoistway or Car Doors (Re-Inspection) | Yes | No | Elevator car door restrictor does not work between the 4ht and 5th floors, needs repaired. Re-inspection required | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 4.2 - Hoistway doors | 8.6.4.13 | Yes | No | Hoistway door safety retainers are missing from all hoistway doors, need to install safety retainers. Re-inspection required |