Inspection
Inspection Details
Equipment ID
11152
11152
Inspection Date
9/24/2024
9/24/2024
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Sean Carmody
Sean Carmody
Mechanic Name
Richard King
Richard King
Relief Valve Pressure
NA
NA
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
18
18
External ID
7a229608-261d-4c95-81d9-a0bf5b04beb4
7a229608-261d-4c95-81d9-a0bf5b04beb4
Location
Station Plaza Limited Partnership
1900 Pine St, St. Louis, MO
Phone: (314) 657-7720
Email: Timothy.Wonsewitz@BCBSMO.COM
1900 Pine St, St. Louis, MO
Phone: (314) 657-7720
Email: Timothy.Wonsewitz@BCBSMO.COM
Owner
Attn: Station Plaza Limited Partnership
Station Plaza Limited Partnership
233 Park Ave, Ste 201, Minneapolis, MN 55415
Phone: (000) 000-0000
Station Plaza Limited Partnership
233 Park Ave, Ste 201, Minneapolis, MN 55415
Phone: (000) 000-0000
Billing
Attn: Jill S. Belsky
Station Plaza Limited Partnership
3630 Grandel Sq, St. Louis, MO 63108
Phone: (314) 454-0800 Ext: 307
Email: jbelsky@rcirealty.com
Station Plaza Limited Partnership
3630 Grandel Sq, St. Louis, MO 63108
Phone: (314) 454-0800 Ext: 307
Email: jbelsky@rcirealty.com
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (I) - Pits | (I)5 | No | No | A code compliant ladder shall be installed in the elevator pit. | 12/9/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.7 - Fire Extinguisher | 8.6.1.6.5 | No | No | A current tested fire extinguisher is required in the elevator machine room. | 12/9/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Display a current state operating certificate. | 12/9/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.8 - Car safeties and guiding members - including roped-hydraulic elevators installed under A17.1b-1989 and later editions | 8.11.3.1.5 (j) Car Safety | Yes | No | A category 5 safety test shall be performed. | 12/9/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | Provide a written MCP. | 12/9/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.5 - Housekeeping | 8.11.2.1.2(e) (Re-Inspection) | No | No | The machine room shall not be used for the storage of non-elevator related material. | 12/9/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.2 - Car top light and outlet | 8.11.2.1.3(b) | No | No | The car top light shall be operational. | 12/9/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.2 Design and Construction of Pits | No | No | The pit shall be kept clean. | 12/9/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The emergency alarm bell shall be operational. | 12/9/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.2-2.27.8 | Yes | Yes | Phase 2 fire service shall be operational. (Maintenance company attempted to fix, but unable to. Unit due for MOD in May 2020). | 12/9/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.8 - Door closing force | 8.11.2.1.1(h) | Yes | No | The door closing force shall be under 30 lbs. | 12/16/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.5 Illumination of Pits | Yes | No | Provide code compliant pit lighting at all areas of the pit. The pit lighting shall be a minimum of 10 ftc. | 12/16/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.2 Design and Construction of Pits | Yes | No | Properly fix the hole in the pit wall near piping. | 12/16/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | Yes | No | An MCP shall be kept on-site. | 12/16/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.3.1.6(h) Phase 2 Audible/Visual Signal (Re-Inspection) | Yes | No | The flashing hat feature on fire service shall be operational when the smoke detectors in the hoistway and machine room are activated. | 12/16/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.22 - Wire rope fastening and hitch plate | 8.11.2.1.3(bb) | Yes | No | The hoist ropes shall be properly secured in the shackles. | 12/16/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 4.1 - Car platform guard | 2.15.9 | Yes | No | The toe guard shall be 48" long. If pit depth in inadequate to support a 48" toe guard a variance shall be applied for. | 12/16/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.4 Access to Pit | Yes | No | The pit ladder shall be code compliant. If a code compliant pit ladder will not fit in the pit a variance shall be applied for. | 12/16/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 4.2 - Hoistway doors | 8.11.2.1.4(b) | Yes | No | The gaps between the hoistway door panels and frames shall not exceed 3/8". If code compliant gaps cannot be achieved, a variance shall be applied for. | 12/16/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. | 1/26/2022 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone shall work. | 12/3/2025 |