Inspection
Inspection Details
Equipment ID
1219
1219
Inspection Date
10/1/2024
10/1/2024
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Robert Kehm
Robert Kehm
Mechanic Name
Jeffrey Miller
Jeffrey Miller
Relief Valve Pressure
440
440
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
21F/20R
21F/20R
External ID
d2da42bb-76a2-4217-aa09-f097fe0ad916
d2da42bb-76a2-4217-aa09-f097fe0ad916
Location
Flynn Park School
7220 WATERMAN AVE, UNIVERSITY CITY, MO
Phone: (314) 565-7646
7220 WATERMAN AVE, UNIVERSITY CITY, MO
Phone: (314) 565-7646
Owner
Attn: Kim Neuhoff
University City School District
8136 Groby Rd, University City, MO 63130
Phone: (314) 290-4099
Email: kneuhoff@ucityschools.org
University City School District
8136 Groby Rd, University City, MO 63130
Phone: (314) 290-4099
Email: kneuhoff@ucityschools.org
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | In cab emergency telephone shall work with 24/7 support. | 11/10/2020 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)4 | No | No | Black mold is growing on machine room walls. Corrective actions shall be taken. | 2/13/2024 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 2/13/2024 |
| A17.1-1996 : Elevators | 1.17 - Standby power operation | 1001.2(a)(17) | Yes | No | The auxiliary lowering operation shall be functional. | 10/4/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection) | Yes | No | The car door shall be restricted from opening when in the closed position anywhere outside the unlocking zone. | 10/4/2022 |
| A17.1-1996 : Elevators | 1.17 - Standby power operation | 211.2 | Yes | No | Emergency lowering shall be operational. | 10/4/2022 |
| A17.1-1996 : Elevators | 1.17 - Standby power operation | 211.2 | Yes | No | Emergency lowering shall be operational and shall conform to 3.26.10.1 through 3.26.10.3. | 11/2/2023 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)8 | Yes | No | Where an additional power source is connected to the load side of the disconnecting means, the disconnecting means required in Section 620-51 shall be provided with an auxiliary contact that is positively opened mechanically and the opening shall not be solely dependent on springs. This contact shall cause the additional power source to be disconnected from it's load when the disconnecting means is in the open position. There wires have been run into the disconnect, but no auxiliary contact has been provided. Emergency lowering operation cannot safely operate without this contact. | 6/20/2024 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 2/13/2024 |
| A17.1-1996 : Elevators | 1.17 - Standby power operation | 211.2 | Yes | No | The auxiliary lowering operation shall be functional. | 6/20/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection) | Yes | No | The car door shall be restricted from opening when in the closed position anywhere outside the unlocking zone. Note: The rear car door doesn't meet this requirement. | 6/20/2024 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)8 | Yes | No | Where an additional power source is connected to the load side of the disconnecting means, the disconnecting means required in Section 620-51 shall be provided with an auxiliary contact that is positively opened mechanically and the opening shall not be solely dependent on springs. This contact shall cause the additional power source to be disconnected from it's load when the disconnecting means is in the open position. There wires have been run into the disconnect, but no auxiliary contact has been provided. Emergency lowering operation cannot safely operate without this contact. (2nd Notice) | 10/1/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection) | Yes | No | The car door shall be restricted from opening when in the closed position anywhere outside the unlocking zone. Note: The rear car door doesn't meet this requirement. (2nd Notice) | 10/1/2024 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone does not work. | 1/14/2025 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | There emergency phone is still not working. Note: The phone had no dial tone and would not call out. (2nd Notice) | 2/13/2025 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)8 | Yes | No | Where an additional power source is connected to the load side of the disconnecting means, the disconnecting means required in Section 620-51 shall be provided with an auxiliary contact that is positively opened mechanically and the opening shall not be solely dependent on springs. This contact shall cause the additional power source to be disconnected from its load when the disconnecting means is in the open position. Elevator lowered with disconnect open (no jumper installed). Auxiliary contact appears to be wired opposite the requirement. | 4/3/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.8 Cleaning of Machine Rooms and Machinery Spaces | No | No | Equipment in the machine room not being used in conjunction with the function or use of the elevator shall be removed. | 4/3/2026 |
| MO Minimum : Elevators | (S) - Fire Service | 8.6.11.1 Monthly Test and Log | No | No | Fire service must be tested and documented monthly. | 4/3/2026 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 4/3/2026 |