Inspection
Inspection Details
Equipment ID
2106
2106
Inspection Date
10/1/2024
10/1/2024
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Raymond Stidham
Raymond Stidham
Mechanic Name
Stephen Long
Stephen Long
Relief Valve Pressure
N/A
N/A
Slide
Stopped Level
Stopped Level
Governor Rope Pull
N/A
N/A
Door Closing Force
Manual
Manual
External ID
863cbfd5-bb77-4dc8-97fb-e6a3659a5a4e
863cbfd5-bb77-4dc8-97fb-e6a3659a5a4e
Location
SBC- Joplin
719 Pearl St, Joplin, MO
Phone: (417) 385-8204
719 Pearl St, Joplin, MO
Phone: (417) 385-8204
Owner
Attn: AT&T Certificate Mgmt
AT&T- Joplin
9780 S Meridian Blvd, Ste 450, Englewood, CO 80112
Phone: (000) 000-0000
Email: ATT.Elevators@LerchBates.com
AT&T- Joplin
9780 S Meridian Blvd, Ste 450, Englewood, CO 80112
Phone: (000) 000-0000
Email: ATT.Elevators@LerchBates.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | springs are not to be used if car exceeds 200 feet/min elevator needs to be slowed down and governor recalubrated | 3/30/2021 |
| A17.1-1996 : Elevators | 5.9 - Buffers and emergency terminal speed limiting devices | 201 | Yes | No | 201.1 spring buffers are not to be used if elevator exceeds 200 frt per min (elevator tacked at 275' per min) | 9/6/2019 |
| A17.1-1996 : Elevators | 2.8 - Pipes, wiring, and ducts | 1001.2(b)(8) | No | No | 2.8 power cables feeding controller (inside controller bare wires showing-covering is breaking down-wiring needs replaced) | 3/30/2021 |
| A17.1-1996 : Elevators | 5.9 - Buffers and emergency terminal speed limiting devices | 201 | Yes | No | Car exceeds max. speed for spring buffers (car currently running 275 f.p.m.) 201.1 | 12/14/2020 |
| A17.1-2016 : Elevators | 1.5 - Car lighting and receptacles | 8.11.3.1.1(e) | No | No | Must Make Car emergency light operable. | 10/13/2025 |
| A17.1-2016 : Elevators | 1.6 - Car emergency signal | 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Must make Emergency Phone Operable. 8.6.4.15 (Currently calling an inactive no. ) | 10/1/2024 |
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 1002.2f | Yes | No | Must make Door open and Door close buttons operable. for proper Fire service phase II operation. 211.7 | 10/1/2024 |
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 211.3a(8) Visual and audible signal | Yes | No | Must make both Audible and Visual Signals operable on Fire service activation. 211.3a(8) | 10/1/2024 |
| A17.1-2016 : Elevators | 1.6 - Car emergency signal | 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Must make Emegency phone operable. 8.6.4.15 | 10/13/2025 |
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 1002.2f | Yes | No | Must Make Door Open and Door Close Buttons Operable. For proper Fire Service Phase II operation 211.7 | 10/13/2025 |
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 211.3a(8) Visual and audible signal | Yes | No | Must make Both Audible and Visual signals operable upon activation of fire service. 211.3a(8) | 10/13/2025 |
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 1002.2f | Yes | No | Must Make Door Open and Door Close Buttons Operable. For proper Fire Service Phase II operation 211.7 |