Inspection
Inspection Details
Equipment ID
17972
17972
Inspection Date
10/2/2024
10/2/2024
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Cynthia "CJ" Brady
Cynthia "CJ" Brady
Mechanic Name
Christian Schickedanz
Christian Schickedanz
Relief Valve Pressure
580
580
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
14F/16R
14F/16R
External ID
aa21173d-124f-4fec-88cb-8b246e60f6c7
aa21173d-124f-4fec-88cb-8b246e60f6c7
Location
Family Care Health Center- STL
4352 Manchester Ave, St. Louis, MO
Phone: (314) 531-5444
4352 Manchester Ave, St. Louis, MO
Phone: (314) 531-5444
Owner
Attn: Family Care Health Center- STL
Family Care Health Center- STL
4352 Manchester Ave, St. Louis, MO 63110
Phone: (314) 531-5444
Email: amitrev@fchcstl.org
Family Care Health Center- STL
4352 Manchester Ave, St. Louis, MO 63110
Phone: (314) 531-5444
Email: amitrev@fchcstl.org
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-2016 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.6.11.1 Firefighters’ Emergency Operation Documentation | No | No | Perform monthly fire service test & document on log in machine room | 10/3/2024 |
| A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.2.1(d) | No | No | Provide complete maintenance control program and post on controller | 10/3/2024 |
| A17.1-2016 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 8.11.3.1.5(a) | No | No | Empty drip pans in the pit & provide covers | 10/3/2024 |
| A17.1-2016 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current state certificate in machine room | 10/3/2024 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)4 | No | No | Remove all non elevator storage from the machine room | 10/3/2024 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current state certificate in machine room | 10/3/2024 |
| MO Minimum : Elevators | (S) - Fire Service | 8.6.11.1 Monthly Test and Log | No | No | Perform monthly fire service test & document on log in machine room | 10/3/2024 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Clean drip pans in the pit & provide covers | 10/3/2024 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 11/8/2024 |
| A17.1-1996 : Elevators | 1.17 - Standby power operation | 211.2 | Yes | No | The auxiliary power lowering operation shall be functional. Note: The UPS will not stay on. | 5/27/2026 |
| A17.1-1996 : Elevators | 2.11 - Disconnecting Means and Control | 210.4 | Yes | No | Where an additional power source is connected to the load side of the disconnecting means, the disconnecting means required in section 620-51 shall be provided with an auxiliary contact that is positively opened mechanically and the opening shall not be solely dependent on springs. This contact shall cause the additional power source to be disconnected from it's load when the disconnecting means is in the open position. Note: A jumper exists from terminal Aux to APE relay contact 32 where the auxiliary contact above should be connected. The additional power source (UPS) should not be functioning until the contact in the disconnect is provided and working. With a jumper in place of the auxiliary contact above and working UPS installed, the elevator could come down on emergency lowering with the main disconnect in the off position, which could present a safety hazard for personnel working on the elevator. | 5/27/2026 |
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 1206.7 | No | No | A record of findings for fire fighters' service operations, tested monthly as required by 8.6.11.1, with identification of the person(s) that performed the operation and the date shall be available on-site. | 5/27/2026 |