Inspection
Inspection Details
Equipment ID
22960
22960
Inspection Date
10/24/2024
10/24/2024
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Gary Beadle
Gary Beadle
Mechanic Name
Jeffrey Woods
Jeffrey Woods
Relief Valve Pressure
Na
Na
Slide
Na
Na
Governor Rope Pull
Na
Na
Door Closing Force
17
17
External ID
6ad9388e-7538-43a9-9cf6-2fc9e9d4e278
6ad9388e-7538-43a9-9cf6-2fc9e9d4e278
Location
4260 Forest Park
4260 Forest Park Ave, Ste 201, St. Louis, MO
Phone: (000) 000-0000
4260 Forest Park Ave, Ste 201, St. Louis, MO
Phone: (000) 000-0000
Owner
Attn: 4260 Forest Park LLC
4260 Forest Park LLC
4260 Forest Park Ave, Ste 201, St. Louis, MO 63108
Phone: (000) 000-0000
4260 Forest Park LLC
4260 Forest Park Ave, Ste 201, St. Louis, MO 63108
Phone: (000) 000-0000
Billing
Attn: Claire Liendecker
4260 Forest Park LLC c/o DCM Group
8300 Eager Rd, Ste 601, St. Louis, MO 63144
Phone: (314) 727-9300 Ext: 121
Alt Phone: (314) 528-9250
Email: cliendecker@dcmstl.com
4260 Forest Park LLC c/o DCM Group
8300 Eager Rd, Ste 601, St. Louis, MO 63144
Phone: (314) 727-9300 Ext: 121
Alt Phone: (314) 528-9250
Email: cliendecker@dcmstl.com
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.8 - Car safeties and guiding members - including roped-hydraulic elevators installed under A17.1b-1989 and later editions | 8.11.2.1.5(j) | Yes | No | Repair guide shoe insert assembly on safety plank, right side. | 2/11/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | Provide MCP | 9/17/2021 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.5.14.3(f) | Yes | No | Auxiliary battery power unit not working | 9/17/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.17 - Drive machine brake | 8.11.2.3.4 | Yes | Yes | Emergency brake failed to hold and maintain floor level on 125% load test. Unit red tagged and removed from service | 9/17/2021 |
| A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.2.1(a) | No | No | Provide MCP | 9/17/2021 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.5.14.3(f) | Yes | No | Auxiliary power unit not working. | 5/10/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.6.11.1 Firefighters Emergency Operation: Monthly Testing | No | No | A record of findings for firefighters' service operation, tested monthly as required by 8.6.11.1 with identification of the person(s) that performed the operation, and the date shall be available on-site. | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.7 - Fire Extinguisher | 8.6.1.6.5 | No | No | An ABC fire extinguisher with a current test tag shall be mounted in the machine room located convenient to the access door. The fire extinguisher is expired. | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.8 - Pipes, wiring, and ducts | 2.8.1 | No | No | All machine room wiring shall be enclosed. Box covers are missing in the machine room closet and shall be provided. | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 4.2 - Hoistway doors | 8.6.4.13 | Yes | No | The top and bottom of horizontally sliding doors shall be provided with a means of retaining the closed door panel in position if the primary guiding means fail. The hoistway door safety retainers are missing from the bottom of the door panel, and shall be installed. | 9/25/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone inoperative. Re-inspection required | 11/29/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.17 - Door and gate equipment | 2.11 | No | No | Need to install missing hoistway door fire tabs | |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current State Elevator Certificate. |