Inspection
Inspection Details
Equipment ID
13215
13215
Inspection Date
10/25/2024
10/25/2024
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Ronald Edwards
Ronald Edwards
Mechanic Name
Justin DeBrot
Justin DeBrot
Relief Valve Pressure
n/a
n/a
Slide
n/a
n/a
Governor Rope Pull
n/a
n/a
Door Closing Force
24
24
External ID
badf6cf3-a703-4ff5-acd6-954dbe7e4c08
badf6cf3-a703-4ff5-acd6-954dbe7e4c08
Location
Forest View
1624 W White Oak St, Independence, MO
Phone: (816) 254-3500
1624 W White Oak St, Independence, MO
Phone: (816) 254-3500
Owner
Attn: Ed Gabel
The Groves
1515 W White Oak St, Independence, MO 64050
Phone: (816) 254-3500
Email: tdavenport@thegroves.com
The Groves
1515 W White Oak St, Independence, MO 64050
Phone: (816) 254-3500
Email: tdavenport@thegroves.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | conversion - reinspect | Yes | No | Non elev.related wiring in hoistway | 9/5/2018 |
| conversion | conversion | conversion - reinspect | Yes | No | Door to mach. room needs to be self closing an self locking | 9/5/2018 |
| conversion | conversion | conversion - reinspect | Yes | No | Non elev. related material in mach. room | 9/5/2018 |
| conversion | conversion | conversion - reinspect | Yes | No | Fire serv. signage in car not correct | 9/5/2018 |
| conversion | conversion | conversion - reinspect | Yes | No | Wiring in hoistway not enclosed | 9/5/2018 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)4 | No | No | materials not nesseary for the maint. or operation of elev. stored in mach. room | 1/10/2019 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | mach. room door needs to be self locking | 1/10/2019 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)4 | No | No | materials in mach. room that are not related to elev. operation | 12/17/2020 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | need self locking doorknob | 12/17/2020 |
| MO Minimum : Elevators | (I) - Pits | (I)8 | No | No | need sump pump cover | 12/17/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | emg phone not working | 12/17/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | phone not working | 8/18/2023 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | didnt have correct fitting to test relief valve | 3/12/2025 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | mach room door lock doesnt lock when door closes | 8/27/2026 |
| A17.1-2016 : Elevators | 1.15 - sign and operating device symbols | 8.6.1.6.7 | No | No | need phase one an two fire serv signage | 8/27/2026 |
| A17.1-2016 : Elevators | 3.3 - Top-of-car operating device | 2.26.1.4 | No | No | car top insp dn button didnt work | 8/27/2026 |
| A17.1-2016 : Elevators | 2.7 - Fire Extinguisher | 8.6.1.6.5 | No | No | out of date |