Inspection
Inspection Details
Equipment ID
26820
26820
Inspection Date
9/30/2024
9/30/2024
Inspection Type
Reinspection
Reinspection
Inspector Name
Curtis Belew
Curtis Belew
Mechanic Name
Benjamin Postawko
Benjamin Postawko
Relief Valve Pressure
NA
NA
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
25
25
External ID
8f64ff23-2b00-49ce-a9d6-3ca28ed8a306
8f64ff23-2b00-49ce-a9d6-3ca28ed8a306
Location
Old Hickory Village
6042 Mid Rivers Mall Dr, St Peters, MO
Phone: (573) 880-3990
Email: cmeyer@brinkmannconstructors.com
6042 Mid Rivers Mall Dr, St Peters, MO
Phone: (573) 880-3990
Email: cmeyer@brinkmannconstructors.com
Owner
Attn: Unk
Old Hickory Village LP
6042 Mid Rivers Mall Dr, St Peters, MO 63304
Phone: (000) 000-0000
Old Hickory Village LP
6042 Mid Rivers Mall Dr, St Peters, MO 63304
Phone: (000) 000-0000
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-2016 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.2.5 Sump Pump Required/Capacity (Re-Inspect) | x | A17.1 - 2016 - 2.2.2.5/ Interpretation record number 10-1496 - The sump control shall not be located in elevator machinery space. It is currently located in the pit and shall be re-located. | 9/30/2024 | |
| A17.1-2016 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.3 | x | x | The fire alarm initiating devices, entrance smoke curtains, heat detector/shunt trip operation, and phase two fire service shall meet the requirements of A17.1 2016 2.27.3. A test was attempted, but problems were encountered, and testing was stopped. | 9/30/2024 |
| A17.1-2016 : Elevators | 1.15 - sign and operating device symbols | 8.6.1.6.7 | x | A car identification number shall be located adjacent to or on every elevator entrance at the designated level, alternate level, and level where means necessary for test is provided - minimum of 3 inches in height. | 9/30/2024 | |
| A17.1-2016 : Elevators | 2.3 - Lighting and receptacles | 2.7.9.1 | x | Permanently installed electric lighting shall be provided in all machinery spaces, machine rooms, control spaces, and control rooms. The illumination shall be not less than 19 fc at the floor level. This applies to the space at the top landing entrance where the means to test is located. | 9/30/2024 | |
| A17.1-2016 : Elevators | 1.15 - sign and operating device symbols | 8.10.2.2.1(o) | x | When the building code requires a sign be posted adjacent to hall call fixtures instructing occupants not to use the elevator in case of fire, the sign show in Fig 2.27.9 shall be provided. The sign shall include only the wording and graphics shown in Fig 2.27.9. When the building code specifies a different design, 2.27.9 shall not apply. The signs installed are different from the ones required by 2.27.9. | 9/30/2024 | |
| A17.1-2016 : Elevators | 1.6 - Car emergency signal | 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | The phone monitoring company shall change their records to reflect the recent change in building name and address so the building can be properly identified in the case of an emergency call. | 9/30/2024 | |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | x | Need to test Unintended Motion (UP) and CommLoss system. | ||
| A17.1-2016 : Elevators | 1.6 - Car emergency signal | 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | Phone volume is extremely low, increase volume. | ||
| A17.1-2016 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | A current State Operating Permit shall be obtained and displayed in the Equipment Room. | |||
| A17.1-2016 : Elevators | 9.19 - Maintenance Records | 8.6.1.2.2(a) On-Site Documentation (Up-to-Date Wiring Diagrams) | Compliant/Required Documentation shall be kept in equipment room(neat/organized) including MCP, Wiring Diagrams, PM log, Callback log, Evacuation procedures, & Unique Testing Procedures. | |||
| A17.1-2016 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.6.11.1 Firefighters’ Emergency Operation Documentation | Fire service testing must be documented monthly. |