Inspection
Inspection Details
Equipment ID
2049
2049
Inspection Date
10/28/2024
10/28/2024
Inspection Type
Reinspection
Reinspection
Inspector Name
Dixon Liljegren
Dixon Liljegren
Mechanic Name
John Osowski
John Osowski
Relief Valve Pressure
n/a
n/a
Slide
n/a
n/a
Governor Rope Pull
n/a
n/a
Door Closing Force
n/a
n/a
External ID
95c2b165-cf39-483e-b88a-5039edee78e5
95c2b165-cf39-483e-b88a-5039edee78e5
Location
Lee's Summit High School
400 SE Blue Pkwy, Lee's Summit, MO
Phone: (816) 986-2000
Email: matthew.tillman@lsr7.net
400 SE Blue Pkwy, Lee's Summit, MO
Phone: (816) 986-2000
Email: matthew.tillman@lsr7.net
Owner
Attn: Nick Mathews
Lee's Summit R-7 School District
502 Transport Dr, Lee's Summit, MO 64081
Phone: (816) 986-2173
Email: nick.mathews@lsr7.net
Lee's Summit R-7 School District
502 Transport Dr, Lee's Summit, MO 64081
Phone: (816) 986-2173
Email: nick.mathews@lsr7.net
Billing
Same as Owner
Violations
Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
---|---|---|---|---|---|---|
MO Minimum : Elevators | (G)2-Alterations | 8.7.2.14.2 Car Enclosure | x | Emergency lights weak. | 1/19/2021 | |
A17.1-2016 : Elevators | 1.16 - Rated load, platform area, and data plate | 2.16.3 | x | no metal data tags | 1/19/2022 | |
MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | x | Machroom door lock defeatable | 1/19/2022 | |
A17.1-2016 : Elevators | 2.8 - Pipes, wiring, and ducts | 8.11.2.1.2(k) | FFS modules in machine room missing covers. | |||
A17.1-2016 : Elevators | 2.14 - Code data plate | 8.11.2.1.2(hh) | Provide code data plate in machine room. | |||
A17.1-2016 : Elevators | 1.18 - Restricted opening of car or hoistway doors | 8.11.2.1.1(r) | x | Provide door restrictors for each car door. | 1/19/2023 | |
A17.1-2016 : Elevators | 2.8 - Pipes, wiring, and ducts | 8.11.2.1.2(k) | Smoke and heat detector wiring exposed, not in conduit. | |||
MO Minimum : Elevators | (S) - Fire Service | 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) | x | Provide covers for FFS modules in machine room. | 9/26/2023 | |
MO Minimum : Elevators | (S) - Fire Service | 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) | x | New smoke detectors present in machine room, but not connected to controller. | 9/26/2023 | |
A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | x | Emergency battery lowering not working. Battery | 4/1/2024 | |
A17.1-2016 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.6.4.19.6 | x | Top of hoistway smoke recalls to wrong floor | 4/1/2024 | |
A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | x | Shunt trip not overriding battery lowering. Need relay added | 4/1/2024 | |
A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | x | Emergency battery lowering inoperable. Bad battery | 2/20/2024 | |
A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | x | Shunt trip battery override needs testing with good battery | 2/20/2024 | |
A17.1-2016 : Elevators | 2.8 - Pipes, wiring, and ducts | 2.8.2 | x | Shunt trip not overriding emergency battery lowering | 10/28/2024 |