Inspection
Inspection Details
Equipment ID
15154
15154
Inspection Date
10/16/2024
10/16/2024
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Cynthia "CJ" Brady
Cynthia "CJ" Brady
Mechanic Name
Dustin Arnett
Dustin Arnett
Relief Valve Pressure
NA
NA
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
21
21
External ID
7c4dc07b-50ce-4652-8bd5-4a7221d854ea
7c4dc07b-50ce-4652-8bd5-4a7221d854ea
Location
City View Apts- Bldg 10
111 N 15th St, Bldg 10, St. Louis, MO
Phone: (314) 588-1177
111 N 15th St, Bldg 10, St. Louis, MO
Phone: (314) 588-1177
Owner
Attn: Rock Rose City View SPE LLC DBA Gateway at City Park
c/o Blue Magma Residential, LLC
13095 Telecom Parkway N, Tampa, FL 33637
Phone: (813) 620-0800
Email: amobley@bmresidential.com
c/o Blue Magma Residential, LLC
13095 Telecom Parkway N, Tampa, FL 33637
Phone: (813) 620-0800
Email: amobley@bmresidential.com
Billing
Attn: Blue Magma Residential, Gateway at City Park Apartments
Blue Magma Residential, Gateway at City Park Apartments
110 N 17th St, St. Louis, MO 63103
Phone: (314) 588-1177
Email: lcapehart@bmresidential.com
Blue Magma Residential, Gateway at City Park Apartments
110 N 17th St, St. Louis, MO 63103
Phone: (314) 588-1177
Email: lcapehart@bmresidential.com
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.6 - Final and emergency terminal stopping devices | 8.11.2.1.3(h) | Yes | Yes | Top final limit shall work before the buffer is compressed. Unit Red-Tagged. | 1/28/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.9 - Buffers and emergency terminal speed limiting devices | 8.11.2.3.6 | Yes | No | The counterweight buffer switch shall work. | 1/28/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.23 - Suspension rope | 8.11.2.1.3(cc) | No | No | The hoist ropes need replacing. | 1/4/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.23 - Suspension rope | 8.11.2.1.3(cc) | No | No | Replace the hoist ropes. | 1/4/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.17 - Door and gate equipment | 8.11.2.1.3(w) | No | No | 8.6.4.3 - Metal hoistway door fire gib is missing on floors 12 & 14. | 1/4/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.23 - Suspension rope | 8.11.2.1.3(cc) | No | No | A rope data tag is required on the suspension ropes. | 1/4/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.20 - Governor rope | 2.18.5 | No | No | 2.18.5.3 - A rope data tag is required on the governor rope. | 1/4/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.28 - Counterweight and counterweight buffer | 2.21 | No | No | 2.21.1.2 - Secure the counterweights in the frame. | 1/4/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.9 - Floor and emergency identification numbering | 2.29.1 | No | No | 2.29.1(g) - Label the crosshead with the elevator number. | 1/4/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.12 - Pipes, wiring, and ducts | 8.11.2.1.3(r) | No | No | Duct covers are missing from the top of the hoistway. | 1/4/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The in car emergency telephone shall be operational. | 10/20/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.11 Periodic Inspection and Test. | Yes | No | Test is incomplete. The following testing items remain: Governor pull out/pull thru, tach governor, tag all devices, and test counterweight buffer. | 10/20/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The in car emergency telephone shall be operational. (2nd Notice) | 12/14/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The in car emergency telephone shall be operational. Violation originally cited on 10/20/22 and still not corrected. Violations shall be corrected within 14 days or elevator will be red tagged and locked out of service. | 3/11/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | The fire extinguisher is expired. A current tested and tagged ABC type fire extinguisher shall be provided in the machine room. | 1/21/2026 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)1 | No | No | A clear path shall be provided to the machine room. Remove paint, supplies, etc. and make a clear path to machine room. | 1/21/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The in car emergency telephone shall be operational (3rd Notice). Per Chief Inspector Gus Guadamuz, 14 days to fix phones or individual units will start being taken out of service. | 8/27/2024 |
| MO Minimum : Elevators | (G)2-Alterations | 8.7.2.14.2 Car Enclosure | Yes | No | Handrails shall be provided on all nonaccess walls. | |
| MO Minimum : Elevators | (G)2-Alterations | 8.7.2.14.2 Car Enclosure | Yes | No | The car enclosure shall be so constructed that removable portions cannot be dismantled from within th car. |