Inspection
Inspection Details
Equipment ID
11220
11220
Inspection Date
10/30/2024
10/30/2024
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Michael Wright
Michael Wright
Mechanic Name
Bruce Dorsey
Bruce Dorsey
Relief Valve Pressure
N/A
N/A
Slide
N/A
N/A
Governor Rope Pull
N/A
N/A
Door Closing Force
21
21
External ID
66f721df-45e8-4706-82b8-0ded7f06f637
66f721df-45e8-4706-82b8-0ded7f06f637
Location
Jackson County Courthouse
415 E 12th St, Kansas City, MO
Phone: (816) 881-3258
Email: bgaddie@jacksongov.org
415 E 12th St, Kansas City, MO
Phone: (816) 881-3258
Email: bgaddie@jacksongov.org
Owner
Attn: Jackson Co Courthouse Facilities Mgmt
Jackson Co Courthouse Facilities Mgmt
415 E 12th St, Kansas City, MO 64106
Phone: (816) 881-3258
Email: FMDAdmin@jacksongov.org
Jackson Co Courthouse Facilities Mgmt
415 E 12th St, Kansas City, MO 64106
Phone: (816) 881-3258
Email: FMDAdmin@jacksongov.org
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (L) - Wire Ropes-Hoisting, Governor and Tiller | (L)12 (Re- Inspection) | Yes | No | Main hoisting ropes undersized. Min.594 actual .588 | 6/29/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.10 - Hoistway construction | 8.11.2.1.3(p) | Yes | No | Seal penetration's and voids in hoistway walls | 6/29/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.4 - Machine space | 8.11.2.1.2(d) | Yes | No | Seal penetrations in machine space | 6/29/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.3.2.1 Phase 1 Emergency Recall OperationBy Fire Alarm initiating Devices | Yes | Yes | Supply test of FFS devices | 6/29/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 4.12 - Standby power selection switch | 8.11.2.2.7 | Yes | No | Supply test of standby power(generator) | 6/29/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current operating certificate in machine room. | 8/30/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 4.2 - Hoistway doors | 8.11.2.1.4(b) | Yes | No | Landing door jamb loose at B level. | 5/17/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone not working, alarm bell ok. | 10/30/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - Door Systems 8.6.4.13 (Re-Inspection) | Yes | No | Landing door jamb loose at basement level. | 10/30/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.11.1 Firefighters' Emergency Operation & Documentation | Yes | No | Provide an audible signal while in recall. | 5/19/2025 |
| A17.1-2016 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.3.1.6(h) Audible/Visual Signal (Re-Inspection) | Yes | No | Provide an audible signal. | 5/21/2026 |
| A17.1-1996 : Elevators | 1.18 - Restricted opening of car or hoistway doors | 111.5 Restricted Opening of Hall/Car Doors | Yes | No | Repair the door restrictor. | 5/21/2026 |
| A17.1-1996 : Elevators | 3.21 - Governor releasing carrier | 1001.2(c)(27) | Yes | No | The mini-ball is not releasing properly when the safties actuate. | 5/21/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Repair the emergency phone. |