Inspection
Inspection Details
Equipment ID
6936
6936
Inspection Date
10/26/2017
10/26/2017
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Unknown Conversion
Unknown Conversion
Mechanic Name
Relief Valve Pressure
Slide
Governor Rope Pull
Door Closing Force
15
15
External ID
Location
Mark Twain Hotel
205 North 9th St, St. Louis, MO
Phone: (314) 231-9110
205 North 9th St, St. Louis, MO
Phone: (314) 231-9110
Owner
Mark Twain Hotel Partners LP
205 North 9th St, St. Louis, MO 63101
205 North 9th St, St. Louis, MO 63101
Billing
Attn: Mark Twain Hotel Partners LP
205 North 9th St, , MO 63101
205 North 9th St, , MO 63101
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | Door restrictor doesn't work | 2/24/2021 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone does not dial out | 9/26/2022 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Excessive amount of debris and trash in pit | 9/26/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency Phone in car fails to establish two-way communication (Busy Signal) | 9/12/2024 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)8 Car Lighting | No | No | Lights in elevator cab shall be guarded to prevent breakage | 10/8/2025 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Testing incomplete. Need to complete annual and category 5 test. Only tested emergency phone, bell, and light. | 10/8/2025 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (1) Minimum Standard | Yes | Yes | After entering the car top it was discovered the hoist ropes and governor rope failed the gauge test. Hoist rope and governor rope shall be replaced. Elevator Red Tagged. | 10/8/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | Yes | Emergency phone is not operational since 2022. Elevator Red Tagged. | 10/8/2025 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | The category 5 portion of the required tested was completed at the time of the hoist/governor rope replacement inspection. The category 1/annual testing items shall be witnessed to complete the annual inspection. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone has no been working since 2022 was not working still at time of hoist/governor rope replacement inspection. The phone shall be made operational by 10/10/25 or the elevator will be red tagged again. |