Inspection
Inspection Details
Equipment ID
10826
10826
Inspection Date
9/11/2024
9/11/2024
Inspection Type
Reinspection
Reinspection
Inspector Name
Sean Carmody
Sean Carmody
Mechanic Name
Brenton Lane
Brenton Lane
Relief Valve Pressure
NA
NA
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
NA
NA
External ID
b31ab6fc-c111-4e06-b992-814f22f25346
b31ab6fc-c111-4e06-b992-814f22f25346
Location
St. Louis Police Department
1200 Clark Ave, St. Louis, MO
Phone: (314) 444-5521
1200 Clark Ave, St. Louis, MO
Phone: (314) 444-5521
Owner
Attn: Rick Ernst
St. Louis City of- Police Dept
1200 Market St, Room 17, St. Louis, MO 63103
Phone: (314) 622-4635
Email: ernstr@stlouis-mo.gov
St. Louis City of- Police Dept
1200 Market St, Room 17, St. Louis, MO 63103
Phone: (314) 622-4635
Email: ernstr@stlouis-mo.gov
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-1996 : Elevators | 1.5 - Car lighting and receptacles | 204.7 | No | No | The cab lighting shall be operational. | 5/21/2020 |
| A17.1-1996 : Elevators | 1.5 - Car lighting and receptacles | 204.7a (3)(a) Standby Illumination in the car. (Re-Inspection) | Yes | No | The emergency lighting shall be operational. | 6/1/2020 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The emergency alarm bell shall be operational. | 6/1/2020 |
| A17.1-1996 : Elevators | 2.7 - Fire Extinguisher | 1001.2(b)(7) | No | No | A current tested ABC type fire extinguisher shall be provided in the elevator machine room. Current extinguisher is expired. | 5/21/2020 |
| A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | All the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) | 5/13/2022 |
| A17.1-1996 : Elevators | 2.36 - Hydraulic Cylinders | 1004.2(b)(19) | No | No | Hydraulic cylinders installed below ground shall conform to A17.1 2016 - Section 8.6.5.8. (Note: I suspect a single bottom jack. The elevator was altered in 2001, but looks as though the original jack was retained. No data exists on site to determine the original install date, but it looks like an old Haughton jack). | 5/13/2022 |
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 211.2-211.8 | Yes | Yes | This unit shall be equipped with firefighter's operation as required by A17.1 1996 Sections 211.5, 1202.12d, 1202.13. (Note: This elevator had a major alteration which included a new controller, pump unit, and fixtures in 2001. It doesn't have firefighter's operation. It's a freight with manual bi-parting doors and isn't equipped with hall call buttons, only car call buttons, but it is an automatic elevator). Elevator is not red tagged. | 5/13/2022 |
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 1206.7 | No | No | Fire service testing must be properly documented monthly on log sheets. There is no log present. | 3/12/2024 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 3/12/2024 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 306.11 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | 2-way communication device shall work. | 9/11/2024 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current state operating permit shall be obtained and displayed in the equipment room. | 4/13/2026 |
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 106.1e Illumination of Pits | No | No | The pit light shall work. Note: Fixture full of water, pit currently dry. | 4/13/2026 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The in car emergency telephone is still not operational. This violation must be corrected immediately per the AHJ. | 3/4/2025 |
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 106.1e Illumination of Pits | No | No | Pit light is not working. | 4/13/2026 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (1) Minimum Standard | Yes | No | Jumpers were not needed to run up to stop ring. Take corrective action and re-test. | 4/13/2026 |