Inspection
Inspection Details
Equipment ID
17586
17586
Inspection Date
10/15/2024
10/15/2024
Inspection Type
Reinspection
Reinspection
Inspector Name
Steven Salabay
Steven Salabay
Mechanic Name
Alex Brinkman
Alex Brinkman
Relief Valve Pressure
600
600
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
NA
NA
External ID
c2bdb5db-42fa-4db4-8d41-b239a0413832
c2bdb5db-42fa-4db4-8d41-b239a0413832
Location
Kipp St Louis High School
706 N Jefferson Ave, St. Louis, MO
Phone: (314) 380-5477
706 N Jefferson Ave, St. Louis, MO
Phone: (314) 380-5477
Owner
Attn: KIPP St. Louis
KIPP St. Louis
1310 Papin St, Ste 203, St. Louis, MO 63103
Phone: (314) 349-1388
Email: bsimmons@kippstl.org
KIPP St. Louis
1310 Papin St, Ste 203, St. Louis, MO 63103
Phone: (314) 349-1388
Email: bsimmons@kippstl.org
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-1996 : Elevators | 1.3 - Operating control devices | 1001.2(a)(3) | No | No | Replace missing direction arrows in return jamb. | 1/13/2020 |
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 1206.2a | Yes | No | Pit shall be clean and dry. | 12/20/2019 |
| A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) | 7/20/2022 |
| A17.1-1996 : Elevators | 1.16 - Rated load, platform area, and data plate | 207 | No | No | The capacity plate shall be located in a conspicuous position inside the car. | 7/20/2022 |
| A17.1-1996 : Elevators | 1.12 - Car enclosure | 204 | No | No | 2.14.1.2.3 - Handrail is missing inside the car. Equipment attached within the car enclosure shall be securely fastened. | 7/20/2022 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 306.11 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The in car emergency telephone shall be operational. A two-way communications means between the car and a location staffed by authorized personnel shall be provided. | 11/3/2022 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)10 Car Floors | No | No | Floor tiles are missing inside the car. All passenger elevator car floors shall be maintained so that persons are not exposed to the hazards of tripping or falling. | 7/20/2022 |
| A17.1-1996 : Elevators | 5.11 Plunger and Cylinder | 1206.5b(4) | Yes | Yes | Elevator red tagged due to blown packing during relief pressure test. Take corrective action and re-test. | 7/11/2023 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | The state certificate is out of date. | 7/11/2023 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (1) Minimum Standard | Yes | Yes | Unit red tagged due to blown packing during relief pressure test. | 10/15/2024 |
| A17.1-1996 : Elevators | 1.17 - Standby power operation | 211.2 | Yes | No | Battery lowering shall work. | 10/15/2024 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Annual test not complete due to packing blowing. Hoistway and fire service shall be tested. | 10/15/2024 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 8/6/2026 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)10 Car Floors | No | No | Floor tiles are damaged inside the car. All passenger elevator car floor shall be maintained so that persons are not exposed to the hazards of tripping or falling. This violation was falsely reported as being corrected on 7/20/22. If violation is not correct by next annual inspection or falsely report as correct again, a re-inspection will be required. | 8/6/2026 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Two way communication device is not functioning and shall be repaired. | |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | |
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 106.1 | No | No | Pits shall be kept clean, dry, and free of equipment or material not relating to the operation of the elevator. |