Inspection
Inspection Details
Equipment ID
7171
7171
Inspection Date
11/6/2024
11/6/2024
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Kurt Zimmerman
Kurt Zimmerman
Mechanic Name
Bradley Tramel
Bradley Tramel
Relief Valve Pressure
Na
Na
Slide
Na
Na
Governor Rope Pull
Na
Na
Door Closing Force
23
23
External ID
74822207-807d-4b9d-87fc-8919d86a22a2
74822207-807d-4b9d-87fc-8919d86a22a2
Location
Downtowner Apartments
1133 Washington Ave, St. Louis, MO
Phone: (314) 875-0111
1133 Washington Ave, St. Louis, MO
Phone: (314) 875-0111
Owner
Attn: EPV2 Downtowner, LLC
EPV2 Downtowner, LLC
125 John Roberts Rd, Ste 12, South Portland, ME 04106
Phone: (000) 000-0000
Email: DTAManager@Eaglepointco.com
EPV2 Downtowner, LLC
125 John Roberts Rd, Ste 12, South Portland, ME 04106
Phone: (000) 000-0000
Email: DTAManager@Eaglepointco.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | Install guard on light top of car | 2/7/2019 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Repair pit light | 2/7/2019 |
| MO Minimum : Elevators | (S) - Fire Service | (S)1 | Yes | No | Repair Fire Service Visual Signage in car | 3/21/2019 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | No | No | Repair Emergency Light & Bell in car | 2/7/2019 |
| A17.1-2016 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.3.3.1(h) Call Cancel Button (Re-Inspection) | Yes | No | Call cancel on fire service phase II is not working correctly. Re-inspection required | 10/25/2023 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | Yes | No | Need to test elevator for operation on emergency power. Re-inspection required | 3/14/2025 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | Yes | No | Need to test elevator for operation on emergency power. Re-inspection required. | 11/19/2025 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | Yes | No | Need to test elevator for operation on emergency power. Re-inspection required. | 4/21/2026 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | Yes | No | Need to test elevator for operation on emergency power. Re-inspection required. | 6/4/2026 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | Yes | No | Need to test elevator for operation on emergency power. Re-inspection required. | 9/2/2026 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | Yes | No | Failed Category 1 Standby Power Test, Reinspection required. | |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Category 5 testing is overdue, recommend performing category 5 test and reinspection of emergency power together on the next inspection. |