Inspection
Inspection Details
Equipment ID
6751
6751
Inspection Date
11/6/2024
11/6/2024
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Mitchell McNeely
Mitchell McNeely
Mechanic Name
Ronald Hogue, Jr
Ronald Hogue, Jr
Relief Valve Pressure
340
340
Slide
Governor Rope Pull
Door Closing Force
19
19
External ID
85cc24dc-4d33-49eb-951c-4dd610c4b672
85cc24dc-4d33-49eb-951c-4dd610c4b672
Location
La Quinta Inn- Sunset Hills
1580 S Kirkwood Rd, St. Louis, MO
Phone: (314) 984-8181
1580 S Kirkwood Rd, St. Louis, MO
Phone: (314) 984-8181
Owner
Attn: La Quinta Inn- Sunset Hills
La Quinta Inn- Sunset Hills
1580 S Kirkwood Rd, St. Louis, MO 63127
Phone: (000) 000-0000
Email: wasi.nisar@nispoint.com
La Quinta Inn- Sunset Hills
1580 S Kirkwood Rd, St. Louis, MO 63127
Phone: (000) 000-0000
Email: wasi.nisar@nispoint.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | 1. Maintenance records shall document compliance with 8.6 of the Code and shall include records of maintenance, repairs, testing, etc. No records available for maintenance per code. | 10/30/2019 |
| conversion | conversion | n/a | No | No | 2. Hoistways and pits shall be kept free of dirt and rubbish and shall not be used for storage purposes. Pit needs to be cleaned. | 10/30/2019 |
| A17.1-1996 : Elevators | 2.1 - Access to machine space | 101.3b | No | No | Machine room needs to be self closing and locking. | 10/30/2019 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone does not work. | 12/13/2021 |
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 106.1e Illumination of Pits | No | No | Pit needs to be cleaned. | 12/1/2020 |
| A17.1-1996 : Elevators | 2.5 - Housekeeping | 1001.2(b)(5) | No | No | Machine room needs to be cleaned. | 12/1/2020 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Current state operating certificate needs to be posted in machine room. | 12/1/2020 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing (Re-Inspect) | Yes | No | This elevator has an overspeed valve device installed that is not sealed and is now required to have a 5 year full load test performed. This requirement is due to the State of Missouri adopting the A17.1 2016 version of the elevator safety code. Overspeed valve shall be tested within 90 days. | 11/1/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.2.1 General Maintenance Requirements Documentation | No | No | A written Maintenance Control Program (MCP) shall be in place to maintain the equipment in compliance with the requirements of 8.6.The MCP shall include but not limited to examinations, tests, cleaning, lubrication, and adjustments to applicable components at regular intervals. | 12/29/2022 |
| MO Minimum : Elevators | (S) - Fire Service | 211.7 Firefighters Operations/Signage | No | No | There is no signage for Firefighters Operation by the phase I key switch. Obtain the correct signage from the building code addition that this elevator was designed to meet. | 12/29/2022 |
| A17.1-1996 : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing (Re-Inspection) | Yes | No | OSV needs to have a full load test performed. Re-inspection required | 1/5/2023 |