Inspection
Inspection Details
Equipment ID
18955
18955
Inspection Date
10/31/2024
10/31/2024
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Steven Salabay
Steven Salabay
Mechanic Name
Brant Willtrout
Brant Willtrout
Relief Valve Pressure
640
640
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
26
26
External ID
65757308-3aad-40a3-91c4-7091ba7791db
65757308-3aad-40a3-91c4-7091ba7791db
Location
Marcus Chesterfield Cine
450 THF Blvd, Chesterfield, MO
Phone: (636) 777-4154
450 THF Blvd, Chesterfield, MO
Phone: (636) 777-4154
Owner
Attn: William Nace
Marcus Chesterfield Cine
450 THF Blvd, Chesterfield, MO 63005
Phone: (636) 777-4154
Email: chesterfield@marcustheatres.com
Marcus Chesterfield Cine
450 THF Blvd, Chesterfield, MO 63005
Phone: (636) 777-4154
Email: chesterfield@marcustheatres.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The in car emergency telephone shall be operational. | 2/12/2021 |
| A17.1-1996 : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing | No | No | This elevator is equipped with an over speed valve that in not sealed. A category 5 test shall be performed on the over speed valve on or before the next annual inspection. The valve shall be sealed and tagged after the category 5 test. | 8/1/2022 |
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 106.1 | No | No | Pit floor needs to be cleaned. | 7/11/2023 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 7/11/2023 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 4/5/2024 |
| A17.1-1996 : Elevators | 1.17 - Standby power operation | 211.2 | Yes | No | The auxiliary power lowering operation shall be functional. | 3/19/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.2.1 Repair Parts | No | No | The missing car operating panel device shall be repaired or replaced. Note: A device on the COP is missing and internal electrical apparatus are partially exposed. It is currently covered by a piece of duct tape. Take corrective action. | 4/5/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.2.1 Repair Parts | No | No | The missing car operating panel device shall be repaired or replaced. Note: A device on the COP is missing and internal electrical apparatus are partially exposed. It is currently covered by a piece of duct tape. Take corrective action. Note: This violation was still not corrected at the time of the 3/19/2024 re-inspection. | 4/5/2024 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 306.11 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone is not working. | 8/15/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.2.1 Repair Parts | Yes | No | The in-car operating panel has button missing with tape over the hole (2nd Notice). Note: This violation has been previously cited and has not been corrected. Re-Inspection is now required. | 8/15/2025 |