Inspection
Inspection Details
Equipment ID
26738
26738
Inspection Date
11/5/2024
11/5/2024
Inspection Type
New Installation
New Installation
Inspector Name
Christopher "RED" Staton
Christopher "RED" Staton
Mechanic Name
Benjamin Postawko
Benjamin Postawko
Relief Valve Pressure
NA
NA
Slide
1"
1"
Governor Rope Pull
50/112
50/112
Door Closing Force
25
25
External ID
b6e7d155-ed4f-49a3-a2fb-6ea05a77c81f
b6e7d155-ed4f-49a3-a2fb-6ea05a77c81f
Location
The Kitchen Mixed Use Building
1300 Woodrail Ave, Columbia, MO
Phone: (573) 289-4610
Email: matt.hollrah@tykheconstruction.com
1300 Woodrail Ave, Columbia, MO
Phone: (573) 289-4610
Email: matt.hollrah@tykheconstruction.com
Owner
Attn: Adam Patchett
P1316 LLC
4240 Philips Farm, Ste 109, Columbia, MO 65201
Phone: (000) 000-0000
P1316 LLC
4240 Philips Farm, Ste 109, Columbia, MO 65201
Phone: (000) 000-0000
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-2016 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.2.5 Sump Pump Required/Capacity (Re-Inspect) | Yes | No | Pit sump pump is required and shall have the capacity to remove a minimum of 3,000 gal/h per elevator (allowing for head pressure resulting from discharge piping height). | 12/16/2024 |
| A17.1-2016 : Elevators | 2.3 - Lighting and receptacles | 2.7.9.1 | Yes | No | Machine room lighting shall not be less than 19fc at floor. | 12/16/2024 |
| A17.1-2016 : Elevators | 3.10 - Hoistway construction | 2.1 | Yes | No | Spaces containing machines, control equipment, sheaves, and other machinery shall be separated from the remainder of the building by a fire-resistive enclosure. Seal hoistway holes and penetrations with approved fire resistant material. | 12/16/2024 |
| A17.1-2016 : Elevators | 3.12 - Pipes, wiring, and ducts | 2.8 | Yes | No | Knockout plugs missing on multiple electrical boxes at the top of the hoistway. | 12/16/2024 |
| A17.1-2016 : Elevators | 3.12 - Pipes, wiring, and ducts | 2.8 | Yes | No | Top of the hoistway has a "flex" electrial run longer than 6' of continuous run. | 12/16/2024 |
| A17.1-2016 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.2.5 Sump Pump Required/Capacity (Re-Inspect) | Yes | No | Pit sump pump discharge piping shall be of fire-resistant/non-combustible materials. All materials contained within the hoistway shall meet minimum fire-resistance rating. | 12/16/2024 |
| A17.1-2016 : Elevators | 3.12 - Pipes, wiring, and ducts | 2.8 | Yes | No | Pit electrical piping shall be of fire-resistant/non-combustible materials. All materials contained within the hoistway shall meet minimum fire-resistance rating. | 12/16/2024 |
| A17.1-2016 : Elevators | 2.11 - Disconnecting Means and Control | 3.26.1 | Yes | No | Disconnects do not meet 30" rule/not co-planer (electrical supply). | 12/16/2024 |
| A17.1-2016 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.3.2 Phase I Operation Recall by Initiating Device | Yes | Yes | Heat devices did not initiate shunt and smokes did not initiate proper floor recalls or Hat operation. | 12/16/2024 |
| A17.1-2016 : Elevators | 3.12 - Pipes, wiring, and ducts | 2.8 | No | No | One knockout plug missing at the top of hoistway. | 1/31/2026 |
| A17.1-2016 : Elevators | 2.43 - Emergency Brake, Ascending Car Overspeed, and Unintended Car Movement Protection | 8.11.2.1.2(ii) | No | No | PBOE (auxillary battery system for drifting car for passenger evacuation), not working, repair and retest. |