Inspection
Inspection Details
Equipment ID
18074
18074
Inspection Date
12/7/2018
12/7/2018
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Tim Crafton
Tim Crafton
Mechanic Name
Relief Valve Pressure
500
500
Slide
Governor Rope Pull
Door Closing Force
24
24
External ID
58e339f2-807e-4c2a-800e-a964c9b61d4a
58e339f2-807e-4c2a-800e-a964c9b61d4a
Location
Eagles Nest Apartments
301 N LORIMIER ST, CAPE GIRARDEAU, MO
301 N LORIMIER ST, CAPE GIRARDEAU, MO
Owner
Riverbend Investments
301 N LORIMIER ST STE 12, CAPE GIRARDEAU, MO 63701-7265
301 N LORIMIER ST STE 12, CAPE GIRARDEAU, MO 63701-7265
Billing
Attn: Riverbend Investments
PO BOX 1364, CAPE GIRARDEAU, MO 63702-1364
PO BOX 1364, CAPE GIRARDEAU, MO 63702-1364
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-1996 : Elevators | 2.4 - Machine space | 101.1a | No | No | A 17.2 ITEM 2.4 MACHINE ROOM WALLS OPEN 2'-3' FROM FLOOR ON ALL FOUR WALLS, SHEETROCK REMOVED. | 8/1/2021 |
| A17.1-1996 : Elevators | 3.5 - Normal terminal stopping device | 1003.3(k) | Yes | No | A17.1 ITEM 3.5 WIRE - UP NORMAL STOP IN SAFETY CIRCUIT, NOT DOOR INTERLOCK CIRCUIT. | 12/9/2019 |
| A17.1-1996 : Elevators | 2.4 - Machine space | 101.1a | No | No | MACHINE ROOM WALLS OPEN 2'-3' UP FROM FLOOR, SHEETROCK REMOVED. (WRITTEN UP IN 2018) | 8/1/2021 |
| A17.1-1996 : Elevators | 3.5 - Normal terminal stopping device | 1003.3(k) | Yes | No | UP NORMAL LIMIT WIRED UP IN DOOR INTERLOCK CIRCUIT. ***RE-INSPECTION REQUIRED*** WRITTEN UP IN 2018 | 2/10/2021 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing | No | No | A17.1 - 8.6.5.16.5 OSV NOT SEALED. PERFORM RQUIRED 5YR TESTING ON OR BEFORE THE NEXT INSPECTION. | 8/1/2021 |
| A17.1-2016 : Elevators | 5.15.2 Unsealed Overspeed Valve | 8.6.5.16.5 (Re-Inspect) | Yes | No | A17.1 - 8.6.5.16.5 OVERSPEED VALVE NOT SEALED, PERFORM REQUIRED 5 YR OSV TESTING WITHIN 90 DAYS PER MISSOURI DEPARTMENT OF FIRE SAFETY/ ELEVATOR SAFETY DIVISION. COMMENY SECOND CITING OF UNSEALED OSV. | 11/29/2022 |
| A17.1-1996 : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing (Re-Inspection) | Yes | No | Elevator is equipped with an overspeed valve that is not sealed. A category 5 test is due on the overspeed valve. | 12/8/2023 |
| A17.1-2016 : Elevators | 2.39 - Low Oil Protection | 8.6.5.12 | Yes | No | Low oil switch is not working. Take corrective action as needed. | 12/8/2023 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 306.11 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone does not work. | 2/26/2024 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (1) Minimum Standard | Yes | No | Unit is leaking excessive oil out of plunger packing. Take corrective action as needed. | 1/27/2026 |