Inspection
Inspection Details
Equipment ID
18872
18872
Inspection Date
11/27/2024
11/27/2024
Inspection Type
5 Year Annual Inspection
5 Year Annual Inspection
Inspector Name
Paul Karrenbrock
Paul Karrenbrock
Mechanic Name
Adam Seiler
Adam Seiler
Relief Valve Pressure
400
400
Slide
na
na
Governor Rope Pull
na
na
Door Closing Force
17
17
External ID
e77327bd-752e-4cb2-82b9-ea672f115d35
e77327bd-752e-4cb2-82b9-ea672f115d35
Location
Compton Gate
2211 S Grand Blvd, St. Louis, MO
Phone: (000) 000-0000
2211 S Grand Blvd, St. Louis, MO
Phone: (000) 000-0000
Owner
Attn: Compton Gate Condo Assoc. c/o Rafco Properties
Compton Gate Condo Assoc
2211 S Grand Blvd, St. Louis, MO 63104
Phone: (000) 000-0000
Compton Gate Condo Assoc
2211 S Grand Blvd, St. Louis, MO 63104
Phone: (000) 000-0000
Billing
Attn: Nicole McGraw
Compton Gate Condo
2211 S Grand Blvd, St. Louis, MO 63104
Phone: (000) 000-0000 Ext: 57518
Alt Phone: (314) 721-8427
Compton Gate Condo
2211 S Grand Blvd, St. Louis, MO 63104
Phone: (000) 000-0000 Ext: 57518
Alt Phone: (314) 721-8427
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | REpair phone in car | 6/17/2020 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current State certificate in machine room | |
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 1206.7 | No | No | Perform monthly fire service testing and document on log in machine room | |
| A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | Maintenance control program shall be provided on site. | |
| A17.1-2016 : Elevators | 5.15.2 Unsealed Overspeed Valve | 8.6.5.16.5 (Re-Inspect) | Yes | No | OSV is not sealed. Perform required testing, seal and tag within 90 days. | 8/22/2023 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency light and phone do not work when normal power is removed. | 8/22/2023 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current State Elevator Certificate. | |
| A17.1-2016 : Elevators | 5.15.2 Unsealed Overspeed Valve | 8.6.5.16.5 (Re-Inspect) | Yes | No | OSV in the pit is unsealed, provide testing. | 11/27/2024 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | Yes | No | Existing battery backup lowering unit is not working correctly, repair as needed. | 11/27/2024 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A copy of the current state operating certificate shall be displayed in the machine room | |
| A17.1-2016 : Elevators | 2.7 - Fire Extinguisher | 8.6.1.6.5 | No | No | Fire extinguisher is expired, have serviced or replaced | |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current State Elevator Certificate. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.9 Cleaning of Top of Cars | No | No | Clean car top. |