Inspection
Inspection Details
Equipment ID
12984
12984
Inspection Date
11/25/2024
11/25/2024
Inspection Type
Reinspection
Reinspection
Inspector Name
Paul Karrenbrock
Paul Karrenbrock
Mechanic Name
Ronald Orr, Jr
Ronald Orr, Jr
Relief Valve Pressure
na
na
Slide
na
na
Governor Rope Pull
na
na
Door Closing Force
na
na
External ID
1885a7cb-4c6f-40e6-a0c0-09f26973ef08
1885a7cb-4c6f-40e6-a0c0-09f26973ef08
Location
Marriott St Louis Grand
900 Washington Ave, St. Louis, MO
Phone: (314) 621-9600
900 Washington Ave, St. Louis, MO
Phone: (314) 621-9600
Owner
Attn: Marriott St. Louis Grand
Marriott St. Louis Grand
800 Washington Ave, St. Louis, MO 63101
Phone: (314) 333-2326
Alt Phone: (314) 418-5858
Email: STLMGEngineering@marriott.com
Marriott St. Louis Grand
800 Washington Ave, St. Louis, MO 63101
Phone: (314) 333-2326
Alt Phone: (314) 418-5858
Email: STLMGEngineering@marriott.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | Left handrail should be replaced due to cracks | 9/12/2025 |
| A17.1-1996 : Escalators | 7.3 - Handrails | 802.2 | No | No | Need to replace right handrail. | 9/12/2025 |
| A17.1-1996 : Escalators | 8.12 - Steps, step chains, and trusses | 802.7 | No | No | Replace all worn step rollers. 8.6.8.7 | 9/12/2025 |
| A17.1-2016 : Elevators | 7.19 - Maintenance records | 8.6.1.2.1(c) | No | No | Provide job specific wiring diagrams. | 9/12/2025 |
| A17.1-2016 : Elevators | 7.19 - Maintenance records | 8.6.1.2.1(a) | No | No | Provide maintenance control program documents. | 9/12/2025 |
| A17.1-1996 : Escalators | 7.3 - Handrails | 802.4 | No | No | Replace both handrails. Splitting noted on outboard and inboard sides. | 9/12/2025 |
| A17.1-1996 : Escalators | 7.5 - Lighting | 805.7 | No | No | Replace step demarcation lights. | 9/12/2025 |
| A17.1-1996 : Escalators | 7.3 - Handrails | 802.4 | No | No | Both handrails need to be replaced due to cracks. | 9/12/2025 |
| A17.1-2016 : Elevators | 8.4 - Drive machine and brake | 8.6.8.15.4 | No | No | Reinspection required, brake torque tests not performed. | 9/12/2025 |
| A17.1-2016 : Elevators | 7.3 - Handrails | 8.6.8.1 | No | No | Left handrail needs replaced | 9/12/2025 |
| A17.1-2016 : Elevators | 7.7 - Combplate and comb step impact device | 8.6.8.15.18 | No | No | Walk on plate switches shall be made operable. | 9/12/2025 |
| A17.1-1996 : Escalators | 7.10 - Operating and safety devices | 805.3a | No | No | The stop button buzzer at the top landing is not sounding and shall be repaired. | 9/12/2025 |
| A17.1-2016 : Elevators | 8.4 - Drive machine and brake | 8.6.8.15.4 | Yes | No | The brake torque could not be tested on the initially due to the need for a specific tool. Reinspection for the brake torque is required. | 10/30/2024 |
| A17.1-2016 : Elevators | 8.4 - Drive machine and brake | 8.6.8.15.4 | Yes | No | The brake torque could not be tested on the initially due to the need for a specific tool. Reinspection for the brake torque is required. REINSPECT IN 14 DAYS | 11/25/2024 |
| A17.1-2016 : Elevators | 8.4 - Drive machine and brake | 8.6.8.15.4 | Yes | Yes | Brake failed torque test. Red-tagged, Re-inspection required | 11/27/2024 |